2019-03-04 14:39:07BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. PROVIDE FLOOR PLAN SHOWING LOCATION OF WINDOWS WITH
 DIMENSIONS OF ROUGH OPENINGS. IF NO CHANGES ARE TO BE
 MADE TO THE ROUGH OPENINGS, PROVIDE STATEMENT THAT
 WINDOWS WILL BE LIKE FOR LIKE. IF OPENINGS ARE ALTERED,
 PROVIDE FRAMING PLAN PER FBCR CHPT. 6.
  
 2. DESIGNER TO SELECT MODEL OF WINDOW AND DOOR TO BE
 INSTALLED FOR EACH OPENING FROM LIST OF AVAILABLE
 MODELS IN PRODUCT APPROVAL. PROVIDE THE PRODUCT COVER
 PAGE AND INDICATE THE SPECIFIC PRODUCT THAT WAS USED ON
 THE INSTALLATION. FBC 107
  
 3. PROVIDE INSTALLATION INSTRUCTIONS FOR EACH MODEL OF
 WINDOW AND DOOR SELECTED.
  