2019-03-15 16:30:50ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THERE IS A MATH ERROR IN THE LOAD CALCULATION. TOTAL
 GENERAL LOAD IS 20,577VA NOT 23,106VA. PLEASE CORRECT.
  
 2. PROVIDE AIC RATING FROM SUPPLY TRANSFORMER. PROVIDE
 CALCULATION TO DEMONSTRATE EQUIPMENT IS SIZED ACCORDING
 TO THE SUPPLY.
 AIC RATING OF SERVICE DISCONNECT AND PANEL
 FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT.
 SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM
 FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT
 NOT LESS THAN 10,000 AMPERES. (110.9)
  
 3. LIGHT FIXTURES IN SHOWER AND TUB AREAS APPEAR TO BE
 FLUSH MOUNT OR RECESSED FIXTURES. THESE FIXTURES NEED
 TO BE VAPOR PROOF.
  
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1.
  
 5. THE TWO 220VOLT OUTLETS LOCATED AT REAR PORCH ARE
 NOT LISTED IN LOAD CALC'S. THIS MAY CHANGE GENERAL LOAD
 CALCULATION. DESCRIBE WHAT THESE OUTLETS WILL BE
 UTILIZED FOR.
  
 6. KITCHEN OUTLETS REQUIRE AFCI PROTECTION. PROVIDE
 NARRATIVE TO INCLUDE ALL CIRCUTS REQUIRING AFCI
 PROTECTION.
 AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING, POWER
 OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI
 AND GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8,
 210.12; FBC RE E3902.16; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
  
 7. OVERCURRENT PROTECTION FOR TANKLESS WATER HEATER IS
 UNDERSUZED.
  
 8. SMOKE DETECTOR LOCATED IN UPSTAIRS HALLWAY CANNOT BE
 WITHIN 3 FEET OF BATHROON DOOR.
  
 9. BEDROOM #4 MISSING SMOKE DETECTOR.
  
 10. DISHWASHER REQUIRES GFCI PROTECTION.
  
 11. RECEPTACLE REQUIRED AT FRONT OF HOUSE.
  
 NOTE: FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  