| 2019-03-15 16:30:50 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. THERE IS A MATH ERROR IN THE LOAD CALCULATION. TOTAL |
| | GENERAL LOAD IS 20,577VA NOT 23,106VA. PLEASE CORRECT. |
| | |
| | 2. PROVIDE AIC RATING FROM SUPPLY TRANSFORMER. PROVIDE |
| | CALCULATION TO DEMONSTRATE EQUIPMENT IS SIZED ACCORDING |
| | TO THE SUPPLY. |
| | AIC RATING OF SERVICE DISCONNECT AND PANEL |
| | FBC R E3606.3AVAILABLE SHORT-CIRCUIT CURRENT. |
| | SERVICE EQUIPMENT SHALL BE SUITABLE FOR THE MAXIMUM |
| | FAULT CURRENT AVAILABLE AT ITS SUPPLY TERMINALS, BUT |
| | NOT LESS THAN 10,000 AMPERES. (110.9) |
| | |
| | 3. LIGHT FIXTURES IN SHOWER AND TUB AREAS APPEAR TO BE |
| | FLUSH MOUNT OR RECESSED FIXTURES. THESE FIXTURES NEED |
| | TO BE VAPOR PROOF. |
| | |
| | 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1. |
| | |
| | 5. THE TWO 220VOLT OUTLETS LOCATED AT REAR PORCH ARE |
| | NOT LISTED IN LOAD CALC'S. THIS MAY CHANGE GENERAL LOAD |
| | CALCULATION. DESCRIBE WHAT THESE OUTLETS WILL BE |
| | UTILIZED FOR. |
| | |
| | 6. KITCHEN OUTLETS REQUIRE AFCI PROTECTION. PROVIDE |
| | NARRATIVE TO INCLUDE ALL CIRCUTS REQUIRING AFCI |
| | PROTECTION. |
| | AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL BRANCH |
| | CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING, POWER |
| | OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI |
| | AND GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8, |
| | 210.12; FBC RE E3902.16; FBC EX 607.1.1 OR 801.1, |
| | 801.2, OR 901.2 AS APPLICABLE. |
| | |
| | 7. OVERCURRENT PROTECTION FOR TANKLESS WATER HEATER IS |
| | UNDERSUZED. |
| | |
| | 8. SMOKE DETECTOR LOCATED IN UPSTAIRS HALLWAY CANNOT BE |
| | WITHIN 3 FEET OF BATHROON DOOR. |
| | |
| | 9. BEDROOM #4 MISSING SMOKE DETECTOR. |
| | |
| | 10. DISHWASHER REQUIRES GFCI PROTECTION. |
| | |
| | 11. RECEPTACLE REQUIRED AT FRONT OF HOUSE. |
| | |
| | NOTE: FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES. |
| | IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| | TAMPER-RESISTANT RECEPTACLES. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |