Plan Review Notes
Plan Review Notes For Permit 19021027
Permit Number 19021027
Review Stop Z
Sequence Number 3
Notes
Date Text
2022-01-04 17:03:36FAILED
  
 1) THE POLE HEIGHT AND STEALTH DESIGN MEET CITY
 STANDARDS. THE POLE COLOR IS TO MATCH THE EXISTING
 DECORATIVE CITY LIGHT POLES (SPECKLED BLACK) LOCATED
 ALONG FERN STREET.
  
 2) REPEAT COMMENT: THE PLANTERS THAT ARE SHOWN ON THE
 SURVEY AND ENGINEERING PLANS ARE SURROUNDED BY A
 STRUCTURAL SOIL SYSTEM THAT IS NOT PERMITTED TO BE
 DISTURBED BY THE INSTALLATION OF THE PROPOSED POLE,
 GROUND RODS, FIBER/POWER PULL BOX AND UNDERGROUND
 ELECTRIC, SO THE CURRENT LOCATION IS NOT APPROVED. THE
 FULL AREA COVERED BY THE STRUCTURAL SOIL UNDER THE
 SIDEWALK IS A MINIMUM OF 19 FEET EAST TO WEST AND THE
 FULL DEPTH OF THE SIDEWALK FROM THE CURB TO THE EDGE OF
 THE RIGHT-OF-WAY LINE. NO EXCAVATION OR INSTALLATION
 MAY OCCUR CLOSER THAN SEVEN (7) FEET FROM A PARALLEL
 LINE WITH THE OUTER EDGES OF THE PLANTER WALLS, FROM
 THE CURB FACE TO THE RIGHT-OF-WAY LINE.
  
 3) THE STAFF HAS MARKED THE SURVEY WITH TWO GREEN
 LINES, THAT ARE APPROXIMATELY 10 FEET APART WHERE YOU
 MAY INSTALL THE POLE, PULL BOX, GROUND RODS, ETC.. THIS
 FINAL LAYOUT IN THIS AREA MUST BE PROVIDED ON A BLOW UP
 INSET WITH DIMENSIONS.
  
 4) THE POLE NEEDS TO BE PUSHED AS CLOSE TO THE CURB AS
 POSSIBLE GIVEN THE OVERHEAD WIRE IN ORDER TO MAINTAIN
 AS MUCH OF A STREET FURNITURE RHYTHM AS POSSIBLE AND TO
 MAINTAIN A UNIFORM SIDEWALK WIDTH BEHIND THE PLANTERS.
  
 5) THANK YOU FOR PROVIDING THE UTILITY POWER PLAN. THE
 POWER PATH IS SHOWN DISTURBING THE STRUCTURAL SOIL
 SYSTEM, WHICH IS NOT PERMITTED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446