Plan Review Notes
Plan Review Notes For Permit 19021006
Permit Number 19021006
Review Stop M
Sequence Number 2
Notes
Date Text
2019-05-01 10:46:382ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19021006
 5/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW WAS NOT COMPLETELY
 ADDRESSED- SEE BELOW AND COMPLY.
  
 1) SHEETS M0003 & M101: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR EF-1, EF-2, EF-3, & EF-6, AND A
 SEQUENCE OF OPERATION FOR EACH FAN- TABLE 403.3.1.1 FBC
 M. A) INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR
 EACH SYSTEM.
  
 2) M101, MED GAS STORAGE EXHAUST: A) THE FIRE DAMPER IS
 PROHIBITED IN THE HAZARDOUS EXHAUST SYSTEM- SECTION
 510.7.1 FBC M. B) THE EXHAUST DUCT SHALL BE ENCLOSED IN
 1-HR FIRE-RESISTANT RATED CONSTRUCTED FROM THE POINT OF
 PENETRATION OF THE FIRE-RATED WALL TO THE OUTLET
 TERMINAL- SECTION 510.7.3 FBC M. C) THE EXHAUST DUCT
 SHALL BE CONSTRUCTED OF G90 GALVANIZED STEEL OR
 NON-METALLIC MATERIALS THAT EXHIBIT A FLAME SPREAD
 INDEX OF 25 AND A SMOKE-DEVELOPED INDEX OF 50 OR LESS
 SECTION 510.9 FBC M. D) MAKEUP AIR SHALL BE PROVIDED AT
 A RATE APPROXIMATELY EQUAL TO THE RATE THAT AIR IS
 BEING EXHAUSTED BY THE SYSTEM- SECTION 510.6.5 FBC M.
 E) PROVIDE THE SEQUENCE OF OPERATION FOR EF-3- SEE
 COMMENT #1 ABOVE.
  
 3) M002: INCOMPLETE DETAILS HAVE BEEN PROVIDED FOR
 MOUNTING THE EF-3 ROOF FAN AND CURB, AND NO DETAILS
 HAVE BEEN PROVIDED FOR RH-1- SEE SECTION 301.15 FBC M
 AND COMPLY. PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 THE INSTALLATIONS, COMPLETE MOUNTING AND ANCHORING
 DETAILS, AND SUBMIT FL. PRODUCT APPROVALS AND/OR
 MIAMI-DADE NOA'S FOR THE UNITS-= RULE 9N-3 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  