| 2019-03-28 07:59:26 | 1ST REVIEW: 19021006 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | MED GAS COMMENTS: |
| | |
| | 1. PROVIDE ROOF DRAWING SHOWING DISTANCE FROM VACUUM |
| | EXHAUST TO AIR INTAKES. PER NFPA 99 |
| | 2. PLEASE STATE ON PLAN WHAT CATEGORY THE MED GAS |
| | SYSTEM IN BEING DESIGNED FOR. PER NFPA 99 |
| | 3. PROVIDE NOTE ON THE PLAN THE CONTRACTOR AND |
| | INSTALLER SHALL BE MED GAS CERTIFIED AND SHALL PROVIDE |
| | CERTIFICATION FOR PERMIT ISSUANCE AND INSPECTIONS. PER |
| | FAC 61G4-15.031(1)(4A)(4B) |
| | 4. PROVIDE ISOMETRIC DRAWING FOR MED GAS INCLUDING |
| | VACUUM EXHAUST. WPB AMEND TO FBC 107.3.5.1.3(13) |
| | 5. PROVIDE PIPING DETAIL OF CONTROL VALVES AND TANK |
| | MANIFOLD ALSO DETAIL OF HOW TANK ARE SECURED. PER WPB |
| | AMEND TO FBC 107.2.1 AND NFPA 99 |
| | 6. NOTE ON THE PLAN THE NUMBER AND SIZE OF TANKS. PER |
| | WPB AMEND TO FBC 107.2.1 AND NFPA 99 |
| | 7. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION |
| | GUIDES FOR ALL MED GAS EQUIPMENT. PER WPB AMEND TO FBC |
| | 107.2.1 AND NFPA 99 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |