| 2019-03-26 16:24:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19021006 |
| | 3/26/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M0003 & M101: PROVIDE EXHAUST VENTILATION |
| | CALCULATIONS FOR EF-1, EF-2, EF-3, & EF-6, AND A |
| | SEQUENCE OF OPERATION FOR EACH FAN- TABLE 403.3.1.1 FBC |
| | M. A) INDICATE HOW MAKEUP AIR IS BEING PROVIDED FOR |
| | EACH SYSTEM AND PROVIDE AIR BALANCE CALCULATIONS- |
| | SECTION 501.4 FBC M. |
| | |
| | 2) M101: AUTOMATIC SHUTOFF DAMPERS, EITHER MOTORIZED OR |
| | GRAVITY, SHALL BE PROVIDED FOR THE O/A SUPPLY DUCTS TO |
| | THE HP'S- SECTION C403.2.4.3 FBC-17 EC |
| | |
| | 3) M101: INDICATE THE TOTAL NUMBER OF CYINDERS AND |
| | TOTAL CU.FT. OF OXYGEN AND NITROUS OXIDE GAS TO BE |
| | STORED IN THE MED GAS CLOSET SECTION 307.1 FBC B. A) |
| | INDICATE HOW THE CYLINDERS WILL BE SECURED IN THE |
| | CLOSET. |
| | |
| | 4) M101: NOTE 1 INDICATES CONDENSATE TO BE DRAINED INTO |
| | THE CITY SANITARY WHICH IS PROHIBITED PER SECTION |
| | 90-126 WPB CODE OF ORDINANCES. PLEASE PROVIDE A |
| | COMPLETE CONDENSATE DISPOSAL PLAN FOR ALL OF THE |
| | HANDLERS- SECTION 307.2.1 FBC M. |
| | |
| | 5) M002: PROVIDE COMPLETE ANCHORING AND MOUNTING |
| | DETAILS FOR THE FANS AND FAN CURBS- SECTION 301.15 FBC |
| | M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |