| 2019-03-22 15:53:36 | BUILDING REVIEW COMMENTS: |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- LIFE SAFETY PLAN SHEET A008 IS SHOWING EGRESS TRAVEL |
| | DISTANCE FROM POINT C TO EXIT #2 PASSING THRU THE WORK |
| | AREA ROOM. LIFE SAFETY PLAN AND ELECTRICAL PLAN ARE |
| | MISSING THE EXIT SIGNS SHOWING THE EGRESS PATH AT THIS |
| | AREA. SEC. 1013.1 FBC. SHOW THE REQUIRED EXIT SIGNS. |
| | |
| | 2- DOOR #13 IN THE BREAK ROOM AREA DOESN'T COMPLY WITH |
| | THE DOOR MANEUVERING CLEARANCE REQUIRED BY SEC. 404.2.4 |
| | FBC-ACCESSIBILITY ON THE PULL SIDE. REVISE AS REQUIRED. |
| | |
| | 3- CHECK-IN COUNTER NEEDS TO COMPLY EITHER WITH SEC. |
| | 904.4.1 FBC-ACCESSIBILITY FOR PARALLEL APPROACH OR SEC. |
| | 904.4.2 FBC-ACCESSIBILITY FOR FORWARD APPROACH. REVISE |
| | PLANS AND DETAIL 1/A503 AS REQUIRED. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |