| Plan Review Notes For Permit 19020970 |
| Permit Number |
19020970 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-03-11 06:42:59 | 1) PER SIZING TABLE 402.4 (2) THE MAXIMUM BTU'S THAT | | | CAN BE CARRIED ON A 1 INCH LINE AT 37 FEET DEVELOPED | | | LENGTH IS 320,000 BTU'S . THE SUBMITTED GAS DRAWING | | | SHOWS A TOTAL BTU LOAD OF 340,000 BTU'S. THE 1 INCH | | | LINE AT THE GAS METER IS UNDERSIZED. | | | 2) PER SIZING TABLE 402.4 (2) THE MAXIMUM BTU'S THAT | | | CAN BE CARRRIED ON A 3/4 INCH LINE AT 37 FEET DEVELOPED | | | LENGTH IS 170,000 BTU'S. THE SUBMITTED GAS DRAWING | | | SHOWS A TOTAL BTU LOAD OF 180,000 BTU'S.. THE 3/4 INCH | | | LINE TO THE TANKLESS WATER HEATER IS UNDERSIZED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|