| 2019-02-25 06:12:11 | 1) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| | G2413.4 (1 ) THROUGH G2413.4 (21). |
| | 2) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| | FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| | SEC. G 2413.4.1, G2413.4.2. |
| | 3) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS |
| | THE ONLY GAS APPLIANCE ON THIS SYSTEM. IF NOT, SUBMIT A |
| | COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF |
| | PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET, |
| | THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM, |
| | THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| | THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM. |
| | 4) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | 5) SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS THE |
| | TYPE OF APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. |
| | 6) ) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER |
| | IS REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| | REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| | BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE |
| | ON THE APPLICATION IN THE DESCRIPTION OF WORK. |
| | 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 8) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | COOKTOP PER THE 2017 FBC-FUEL GAS CODE SEC.304.1, 614.6 |
| | (CLOTHES DRYERS) OR 2017 FBC-RES. SEC.G 2407.1. |
| | 9) SOUTH FLORIDA PLUMBING AND BACKFLOW IS LISTED AS THE |
| | CONTRACTOR ON THE PERMIT APPLICATION BUT CR HOME |
| | SERVICES LLC IS LISTED ON THE CONTRACTOR INVOICES. |
| | SUBMIT INFORMATION AS TO WHAT CAPACITY CR HOME SERVICES |
| | IS INVOLVED IN THIS PROJECT. WPB AMEND. TO FBC SEC. |
| | 107.2.1, FL. STATUTES 489.105. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |