| 2019-03-25 10:49:03 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1) DIGITAL SUBMITTED PLANS ARE REQUIRED TO BE SIGNED |
| | DIGITALLY. RULE 61G15-23. PLEASE RESUBMIT ALL PLANS |
| | WITH A DIGITAL SIGNATURE. |
| | |
| | 2) PROVIDE A SANITARY RISER AND WATER DISTRIBUTION |
| | RISER DRAWING. FBC 107.3.5 |
| | |
| | 3) PROVIDE WHERE HOT WATER SUPPLY IS COMING FROM FOR |
| | THE EMPLOYEE SINK AND THE TOTAL DEVELOPED LENGTH OF |
| | THAT LINE. IF OVER 50' A RETURN SYSTEM WILL BE NEEDED. |
| | FBC-P 607.2 |
| | |
| | 4) PROVIDE MOUNTING HEIGHT OG THE REAR AND SIDE GRAB |
| | BAR ON SHT.A2.1 |
| | |
| | 5) SHT.CS1.0 CALLS OUT BUILDING AS 3604 SQUARE FEET. |
| | PALM BEACH COUNTY PROPERTY'S APPRAISERS OFFICE LIST |
| | SQUARE FOOTAGE AS 4257. PLEASE CLARIFY OR CHANGE TO |
| | CORRECT SQUARE FOOTAGE AND OCCUPANT LOAD. FBC 107.2.1 |
| | |
| | 6)PROVIDE CLEAR FLOOR SPACE FOR STAFF BREAK ROOM SINK |
| | AREA WITH HEIGHT. FBC-A 606.2, 606.3 |
| | |
| | 7) PROVIDE DRINKING FOUNTAIN DETAIL SHOWING IT IS TO |
| | COMPLY WITH FBC0A 602. |
| | |
| | 8)SHT.A2.1 SHOWS TOILET DISPENSER HEIGHT BUT IS NOT |
| | SHOWING DISTANCE FROM BOWL. FBC-A 604.7 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |