2019-03-26 13:09:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020967
 3/26/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M101 & M102: REFER TO SECTION 809.2 FBC-17
 EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE
 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) M101 & M102: PROVIDE AN EQUIPMENT SCHEDUKLE FOR THE
 EXISTING FCU-1, AND RENAME THE FCU FOR THE VAULT AS
 FCU-2 TO AVOID CONFUSION.
  
 3) M101: PROVIDE A DUCT MOKE DETECTORS IN THE SUPPLY
 AIR SYSTEMS OF THE EXISTING FCU-1- SECTION 606.2.1.
  
 4) M101: THE LOCATION OF THE NEW O/A INTAKE FIOR THE
 EXISTING FCU-1 APPEARS TO BE WITHIN THE REQUIRED 10'
 CLEARANCE DISTANCE TO THE REAR PARKING LOT- SEE SECTION
 401.4 (2) FBC M.
  
 5) M101: SUBMIT MANUFACTURER'S SPECIFICATIONS AND A
 MIAMI-DADE NOA AND/OR A FL. PRODUCT APPROVAL FOR THE
 O/A INTAKE LOUVER- SEE SECTION 401.5 FBC M.
  
 6) M101 & M102: KEYED NOTES 8 AND 9 INDICATE EXHAUST
 DUCTS RUNNING FROM THE VAULT FCU. THIS APPEARS TO BE A
 MISTAKE. IS THIS SYSTEM AN ERV WITH ONE OF THOSE DUCTS
 INTENDED TO BE O/A INTAKE? THE EQUIPMENT SCHEDULE DOES
 NOT LIST ANY EXHAUST CFMS.
  
 7) M103: THE CONDENSING SUPPORT STAND DOES NOT PROVIDE
 COMPLETRE ENGINEERING AND DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOFTOP CONDENSER. PLEASE PROVIDE
 SITE SPECIFIC ENGINERRING- SECTION 301.15 FBC M AND SEE
 TABLE 1510.10 FBC -B FOR REQUIRED CLEARANCE UNDER THE
 UNIT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  