| 2019-03-26 13:09:54 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020967 |
| | 3/26/2019 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M101 & M102: REFER TO SECTION 809.2 FBC-17 |
| | EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE |
| | 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT |
| | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR |
| | AIR. |
| | |
| | 2) M101 & M102: PROVIDE AN EQUIPMENT SCHEDUKLE FOR THE |
| | EXISTING FCU-1, AND RENAME THE FCU FOR THE VAULT AS |
| | FCU-2 TO AVOID CONFUSION. |
| | |
| | 3) M101: PROVIDE A DUCT MOKE DETECTORS IN THE SUPPLY |
| | AIR SYSTEMS OF THE EXISTING FCU-1- SECTION 606.2.1. |
| | |
| | 4) M101: THE LOCATION OF THE NEW O/A INTAKE FIOR THE |
| | EXISTING FCU-1 APPEARS TO BE WITHIN THE REQUIRED 10' |
| | CLEARANCE DISTANCE TO THE REAR PARKING LOT- SEE SECTION |
| | 401.4 (2) FBC M. |
| | |
| | 5) M101: SUBMIT MANUFACTURER'S SPECIFICATIONS AND A |
| | MIAMI-DADE NOA AND/OR A FL. PRODUCT APPROVAL FOR THE |
| | O/A INTAKE LOUVER- SEE SECTION 401.5 FBC M. |
| | |
| | 6) M101 & M102: KEYED NOTES 8 AND 9 INDICATE EXHAUST |
| | DUCTS RUNNING FROM THE VAULT FCU. THIS APPEARS TO BE A |
| | MISTAKE. IS THIS SYSTEM AN ERV WITH ONE OF THOSE DUCTS |
| | INTENDED TO BE O/A INTAKE? THE EQUIPMENT SCHEDULE DOES |
| | NOT LIST ANY EXHAUST CFMS. |
| | |
| | 7) M103: THE CONDENSING SUPPORT STAND DOES NOT PROVIDE |
| | COMPLETRE ENGINEERING AND DESIGN CRITERIA FOR |
| | INSTALLATION OF THE ROOFTOP CONDENSER. PLEASE PROVIDE |
| | SITE SPECIFIC ENGINERRING- SECTION 301.15 FBC M AND SEE |
| | TABLE 1510.10 FBC -B FOR REQUIRED CLEARANCE UNDER THE |
| | UNIT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |