2019-03-27 18:48:07COMMERCIAL CHANGE OF OCCUPANCY, BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- SHEET CS1.0:
 A)ACCORDING TO OCCUPANCY LOAD (88 PERSONS) SHOWN ON
 SHEET CS1, TWO EXITS ARE REQUIRED. SEC. 1006.2.1 FBC.
 LIFE SAFETY PLAN ON SAME SHEET SHOWS ONLY ONE EXIT FOR
 THE RETAIL AREA TO THE MAIN ENTRY DOORS AND ONLY ONE
 EXIT FOR THE SALES COUNTER AREA TO THE REAR DOORS. THE
 TWO EXITS OPTIONS ARE REQUIRED FOR FOR ALL THE PERSONS
 IN THIS ESTABLISHMENT. REVISE AS LIFE SAFETY PLAN AS
 REQUIRED SHOWING BOTH EXITS AVAILABLE FOR EVERYBODY.
  
 B)CLARIFY HOW EGRESS THROUGH THE SALES COUNTER AREA
 FROM THE RETAIL AREA IS GOING TO BE ACHIEVED SINCE THE
 DOORS LEADING TO THIS AREA SEEM TO BE LOCKED. SEC.
 1016.2 FBC DOESN'T ALLOW EGRESS THROUGH INTERVENING
 SPACES THAT CAN BE LOCKED.
  
 C)CLARIFY OCCUPANT LOAD CALCULATIONS. WHY USING 1:15
 SQUARE FOOTAGE FOR WAITING AREA. CLARIFY IF USING GROSS
 OR NET AREAS. CLARIFY USE. SEE TABLE 1004.1.2 FBC.
 ALSO, CLARIFY HOW THE AREAS FOR WAITING, RETAIL,
 STORAGE/STOCK WERE CALCULATED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- BASED ON THE REQUIRED NUMBER OF EXITS REQUIRED BY
 THE OCCUPANT LOAD SHOWN ON SHEET CS1.O BOTH EXITS NEED
 TO BE ACCESSIBLE MEANS OF EGRESS. PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE REAR EXIT COMPLIES WITH
 THE ACCESSIBLE MEANS OF EGRESS. SEC. 1012.8 FBC
 EXISTING BUILDING. SEC. 207 FBC-ACCESSIBILITY AND SEC.
 1007.1 2003 INTERNATIONAL BUILDING CODE.
  
 3- CLARIFY BUILDING USE SHOWN ON THE BUILDING CODE
 INFORMATION: THIS IS NOT ALTERATION LEVEL 2. ACCORDING
 TO SEC. 506 FBC-EXISTING BUILDING THIS IS A CHANGE OF
 OCCUPANCY. THE BUILDING IS CURRENTLY USED AS BUSINESS
 OCCUPANCY. REVISE AS REQUIRED.
  
 4- FLOOR PLAN ON SHEET A1.0: DOORS 03A AND O3B DON'T
 SEEM TO COMPLY WITH DOOR MANEUVERING FOR FRONT
 APPROACH. FLOOR PLAN SHOWS 1'-5-1/4". NEED 18 INCHES
 MIN AS REQUIRED BY SEC. 404.2.4 FBC-ACCESSIBILITY.
 REVISE AS REQUIRED.
  
 5- WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM
 SHALL COMPLY WITH SEC. 603 AS REQUIRED BY SEC. 213.2
 FBC-ACCESSIBILITY. EXISTING TOILET ROOM SHOWN ON FLOOR
 PLAN NEEDS TO COMPLY ALSO. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE (INCLUDING DOOR).
  
 6- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved