Plan Review Notes
Plan Review Notes For Permit 19020956
Permit Number 19020956
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-04 14:55:56CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 DERM=PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL
 RESOURCES MANAGEMENT
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 DERM=PBC DEPARTMENT OF ENVIRONMENTAL RESOURCES
 MANAGEMENT
  
 1ST REVIEW PLUMBING
 A SEPARATE PERMIT IS REQUIRED FOR IRRIGATION
 A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTORS
 A SEPARATE PERMIT IS REQUIRED FOR THE POTABLE WATER
 SERVICE BACKFLOW PREVENTER
 A SEPARATE PERMIT IS REQUIRED FOR STAND-BY GENERATOR.
 EMERGENCY STAND-BY GENERATOR. PROVIDE STORAGE CAPACITY
 AND VENTING DETAILS OF SUB BASE FUEL TANK PER WPB FBC
 107.2.1. IF STORAGE CAPACITY IS GREATER THAN 550
 GALLONS THEN DERM APPROVAL IS REQUIRED.
 PLUMBING COMMENTS: DENIED
  
 1ST REVIEW: DENIED
  
 I. RE: GENERAL
 NO COMMENT
  
 II. RE: FBC ACC
 A. A3.3
 1. LAVATORY SHALL NOT BE LOCATED IN THE CLEARANCE
 ADJACENT TO THE SHOWER CONTROLS PER FBC ACC 608.2.2.1.
 2. FLUSH CONTROL SHALL BE ON OPEN SIDE OF WATER CLOSET
 PER FBC ACC 604.6.
 3. PROVIDE INSIDE TURNING RADIUS FOR WATER CLOSET
 ACCESS IN ACCORDANCE WITH FBC ACC 304.3.
 4. NOTES FOR DRINKING FOUNTAIN DETAIL SHALL REFERENCE
 FBC 2017 EDITION, NOT 2014.
 5. TOILET ACCESSORY ?E?- HCP ACCESSIBLE SHOWER CONTROL.
 IN ACCORDANCE WITH FBC ACC 608.6, ADD VERBAGE TO NOTE
 ?FIXED OR LOW POSITION OF SHOWER HEAD TO BE MAXIMUM 48
 INCHES ABOVE SHOWER FLOOR.?
 6. SECTION AT HC SINK; 27? MIN SHOULD BE TO THE BOTTOM
 SIDE OF LEDGE, NOT TO THE CURVATURE OF THE BOWL.
 7. PER WPB FBC 107.2.1, PROVIDE ALL DIMENSIONS FOR THE
 FOLLOWING AS REQUIRED IN FBC ACC:
 A. 603.3; MIRROR TO BE MAXIMUM 40? AFF, NOT 48?.
 B. 604.4; TOP OF WATER CLOSET SEAT RANGE 17?-19?
 C. 604.5.1; SIDE GRAB BAR FOR WATER CLOSET
 E. 604.5.2; REAR GRAB BAR FOR WATER CLOSET
 F. 604.5.7; TOILET PAPER DISPENSER OUTLET
 G. 608.3.2; SHOWER GRAB BARS
 H. 608.5.2; SHOWER CONTROL LOCATION
 B. A3.4
 1. INDICATES A CABINET MOUNTED SERVICE SINK FOR THE MOP
 SINK. THE PLUMBING FIXTURE SCHEDULE INDICATES A FLOOR
 MOUNTED SINK AND PLUMBING DETAIL SHOWS THE SAME. PER
 WPB FBC 107.2.1, PLEASE CLARIFY. AS THE DETAIL ON A3.4
 SHOWS A BARRIER FREE APPLICATION IN THE ELEVATION,
 SHOULD THAT APPLICATION PREVAIL, THE SINK WOULD HAVE TO
 MEET ALL REQUIREMENTS OF FBC ACC AND THE SINK FLOOD
 LEVEL RIM ELEVATION WOULD HAVE TO COMPLY WITH THE
 REQUIREMENTS AND THE CABINET TOP HEIGHT WOULD HAVE TO
 ACCOMMODATE THAT. THE PLUMBING FIXTURE SCHEDULE WOULD
 NEED TO BE REVISED TO REFLECT THAT. THE CLEAR SPACE
 REQUIREMENTS FOR PARALLEL APPROACH AND CENTER LINE
 DIMENSION FROM SIDE WALL WOULD NEED TO BE PROVIDED.
  
 III. RE: SANITARY
 A. PER WPB FBC 107.2.1, PROVIDE DRAINAGE FOR WALK IN
 COOLER AND WALK IN FREEZER EVAPORATORS. COMPLY WITH FBC
 PL CHAPTER 8.
 B. PER FBC PL 914.2, CIRCUIT VENT CONNECTION (VERTICAL
 DRY VENT) SHALL BE LOCATED BETWEEN THE TWO MOST
 UPSTREAM FIXTURE DRAINS. THE VENT SHALL CONNECT TO THE
 HORIZONTAL BRANCH AND SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTION 905. THE CIRCUIT VENT PIPE SHALL NOT
 RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. FIXTURE
 BRANCH SERVING THE CLOTHES WASHER, MOP SINK AND
 DRINKING FOUNTAIN SHALL CONNECT TO THE HORIZONTAL
 BRANCH DRAIN/VENT DOWNSTREAM OF THE TWO WATER CLOSET
 FIXTURE DRAINS IN ORDER TO COMPLY WITH FBC PL 914.5.
 C. PER FBC PL 1003.6, PROVIDE A LINT INTERCEPTOR FOR
 THE CLOTHES WASHER DRAIN.
  
 IV. RE: STORM DRAINAGE
 A. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR SIZING
 OF DOWNSPOUT SCUPPERS, DOWNSPOUTS AND OVERFLOW
 SCUPPERS. PROVIDE CODE OR STANDARD OR FORMULA USED FOR
 CALCULATION. INCLUDE THE VERTICAL PARAPET WALLS IN
 CALCULATIONS.
  
 V. RE: WATER SERVICE & DISTRIBUTION
 A. PROVIDE A BACKFLOW PREVENTER FOR POTABLE WATER
 SERVICE PER FBC PL 608.4.
 B. P-2.2 AND P-3.2 SHOW 1-1/2? SERVICE. C2.1 SHOWS 2?
 SERVICE. PLEASE CLARIFY AND CORRECT PLANS AS NEEDED PER
 WPB FBC 107.2.1.
 C. PER WPB FBC 107.2.1, PROVIDE DETAIL OF UNDERGROUND
 SLEEVE FOR HW, HWR, AND CW TO COOKING ISLAND. INCLUDE
 SIZE OF SLEEVE, MATERIAL, PULL STATIONS/END TERMINALS
 AND DETAIL OF HOT WATER INSULATION AND HOW APPLIED.
  
 VI. RE: IRRIGATION PLANS L2.0 AND L3.0.
 A. L.2 IRRIGATION LEGEND INDICATES PVB BACKFLOW
 PREVENTION. DEVICE SHALL BE RPZ PER WPB CCC WITH TYPE L
 OR K COPPER TO INLET AND SHALL BE LEAD FREE.
 B. L3.0 INDICATES A WELL AND PUMP AS WELL AS TWO (2)
 TYPES OF BACKFLOW PREVENTION. PLEASE REMOVE
 NON-APPLICABLE DETAILS FROM PLAN AND INDICATE THE
 APPLICABLE DEVICE AS RPZ, LEAD FREE, PER WPB CCC WITH
 TYPE L OR K COPPER TO INLET AND SHOW LOCATION ON L.2
 PER WPB FBC 107.2.1.
 C. PER WPB FBC 107.2.1, SHOW LOCATION OF RAIN SENSOR
 DEVICE, TIME CONTROLLER AND PERTINENT CONTROL VALVES
 (THAT IS TO SAY, IDENTIFY THE CONTROL VALVES ON THE
 PLAN THAT CONTROL THE NEW WORK) ON L2.0.
  
 VII. RE: PLUMBING FIXTURE SCHEDULE
 A. THE PLUMBING FIXTURE SCHEDULE ON P-4.0 INDICATES A
 FLOOR MOUNTED SINK AND DETAIL ON A-3.3 SHOWS THE SAME.
 THE DETAIL ON A3.4 SHOWS A BARRIER FREE APPLICATION IN
 THE ELEVATION. PER WPB FBC 107.2.1, PLEASE CLARIFY.
 SHOULD THE DETAIL ON A3.4 PREVAIL, THE SINK WOULD HAVE
 TO MEET ALL REQUIREMENTS OF FBC ACC AND THE SINK FLOOD
 LEVEL RIM ELEVATION WOULD HAVE TO COMPLY WITH THE
 REQUIREMENTS AND THE CABINET TOP HEIGHT WOULD HAVE TO
 ACCOMMODATE THAT. THE PLUMBING FIXTURE SCHEDULE WOULD
 NEED TO BE REVISED TO REFLECT THAT. THE CLEAR SPACE
 REQUIREMENTS FOR PARALLEL APPROACH AND CENTER LINE
 DIMENSION FROM SIDE WALL WOULD NEED TO BE PROVIDED.
 B. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION SHEETS/MANUAL FOR GDRU?S.
 C. HAND HELD SHOWER SHALL BE PROVIDED WITH A VACUUM
 BREAKER.
  
 VIII. RE: KITCHEN EQUIPMENT SCHEDULE:
 A. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION SHEETS/MANUAL FOR ALL EQUIPMENT.
 B. PER WPB FBC 107.2.1, PROVIDE FOR THE FOLLOWING ITEMS
 THIS INFORMATION; WILL BACKFLOW PREVENTION PROTECTION
 BE PROVIDED THROUGH AN AIR GAP OR BY MEANS OF A
 BACKFLOW PREVENTION DEVICE? PLEASE SPECIFY ON THE PLANS
 PER WPB FBC 107.2.1 AND IF DEVICE IS REQUIRED PROVIDE
 APPLICABLE ASSE STANDARD. IF INTERNAL BACKFLOW
 PREVENTION IS PROVIDED IN EQUIPMENT THEN INDICATE AND
 PROVIDE APPLICABLE NSF STANDARD.
 1. ITEM A, ELECTRIC TILTING BRAISING PAN
 2. ITEM E, BOILERLESS CONVECTION STEAMERS
 3. ITEM G, GAS FIRED KETTLES
 4. ITEM M, CONVEYOR DISHWASHER
  
 END OF COMMENTS
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, AA TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  
  
  