Plan Review Notes
Plan Review Notes For Permit 19020956
Permit Number 19020956
Review Stop M
Sequence Number 1
Notes
Date Text
2019-04-09 10:51:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19020956
 4/9/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BACH AMENDMENTS TO THE FBC SIXTH EDITION
 2017
  
 PLAN REVIEW RESULTS: DENIED.
 PLEASE REVIEW THE COMMENTS LISTED BELOW AND RESUBMIT
 CORRECTED PLANS
  
 1) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE KITCHEN EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS,
 AND THE WALK-IN FREEZERS- SECTION 107.2.1 WPB.
  
 2) PROVIDE A KITCHEN EQUIPMENT PLAN AND EQUIPMENT
 SCHEDULE- SECTION 107.2.1 WPB.
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 GAS-FIRED COOKING APPLIANCES AND THE GAS WATER HEATERS-
 SECTIONS 623.1 & 624.1 FBC FG.
  
 4) SHEET M2.0: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE COOKING APPLIANCES- SECTION 304.1 FBC FG.
  
 5) M1.1: THE COMBUSTION AIR INTAKES FOR THE GAS WATER
 HEATERS APPEAR TO BE IN PROXIMITY OF THE EXHAUST OUTLET
 FOR KEF-1. PLEASE PROVIDE CLEARANCE DISTANCE
 MEASUREMENTS PER THE MANUFACTURER'S INSTALLATION
 GUIDELINES- SECTION 303.1 FBC FG.
  
 6) M2.0: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE CHEMICAL AND CLEANING STORAGE, TRASH, LAUNDRY, AND
 LOCKER ROOMS- TABLE 403.3.1.1 FBC M. PROVIDE A SEQUENCE
 OF OPERATION FOR THE FANS- SECTION 501.4 FBC M.
  
 7) M1.1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 DRYER, AND PROVIDE A DRYER EXHAUST DIAGRAM SHOWING THE
 TOTAL RUN LENGTH OF THE DUCT FROM THE DRYER OUTLET TO
 THE TERMINATION LOCATION- SECTIONS 504.1 AND 504.8.4
 FBC M. PLEASE NOTE THAT MAKEUP AIR IS REQUIRED FOR
 DRYERS EXHAUSTING MORE THAN 200 CFMS- SECTION 504.6 FBC
 M
  
 8) M1.1: PROVIDE DUCT SMOKE DETECTORS IN THE SUPPLY
 SYSTEMS OF AHU-1 & 2- SECTION 606.2.1 FBC M.
  
 9) M1.1: ALTHOUGH KEF-1 & 2 ARE UNDER SEPARATE PERMIT,
 PLEASE VERIFY EXHAUST OUTLET CLEARANCE DISTANCES IN
 ACCORDANCE WITH SECTIONS 506.3.13.2 & 506.3.13.3 FBC M
 LISTED BELOW.
  
 506.3.13.2 TERMINATION THROUGH AN EXTERIOR WALL.
 EXHAUST OUTLETS SHALL BE PERMITTED TO TERMINATE THROUGH
 EXTERIOR WALLS WHERE THE SMOKE, GREASE, GASES, VAPORS
 AND ODORS IN THE DISCHARGE FROM SUCH TERMINATIONS DO
 NOT CREATE A PUBLIC NUISANCE OR A FIRE HAZARD. SUCH
 TERMINATIONS SHALL NOT BE LOCATED WHERE PROTECTED
 OPENINGS ARE REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING. OTHER EXTERIOR OPENINGS SHALL NOT BE LOCATED
 WITHIN 3 FEET (914 MM) OF SUCH TERMINATIONS.
  
 506.3.13.3 TERMINATION LOCATION.
 EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET
 (3048 MM) HORIZONTALLY FROM PARTS OF THE SAME OR
 CONTIGUOUS BUILDINGS, ADJACENT BUILDINGS AND ADJACENT
 PROPERTY LINES AND SHALL BE LOCATED NOT LESS THAN 10
 FEET (3048 MM) ABOVE THE ADJOINING GRADE LEVEL. EXHAUST
 OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) HORIZONTALLY FROM OR NOT LESS THAN 3 FEET (914 MM)
 ABOVE AIR INTAKE OPENINGS INTO ANY BUILDING.
  
 10) COMMISSIONING OF THE MECHANICAL SYSTEMS ARE
 REQUIRED IN ACCORDANCE WITH SECTION C408.2 FBC EC.
 MECHANICAL SYSTEMS AND SERVICE WATER-HEATING SYSTEMS
 COMMISSIONING AND COMPLETION REQUIREMENTS.
 PRIOR TO THE FINAL MECHANICAL AND PLUMBING INSPECTIONS,
 THE LICENSED DESIGN PROFESSIONAL, ELECTRICAL ENGINEER,
 MECHANICAL ENGINEER OR APPROVED AGENCY SHALL PROVIDE
 EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING AND
 COMPLETION IN ACCORDANCE WITH THE PROVISIONS OF THIS
 SECTION.
 REFER TO SECTION C408.2.1 AND PROVIDE A COMMISSIONING
 PLAN.
  
 11) GENERATOR: A) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND THE UL CERTIFICATE OF COMPLIANCE- SECTION 915.1 FBC
 M. B) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 EXHAUST PIPE AND PROVIDE A DIAGRAM SHOWING THE PIPE RUN
 FROM THE GENERATOR TO TERMINATION LOCATION ABOVE THE
 ROOF. C) PROVIDE ENGINEERED DETAILS SHOWING HOW THE
 PIPE WILL BE SUPPORTED AND ATTACHED TO THE BUILDING-
 SECTION 301.15 FBC M. D) PROVIDE BACKPRESSURE
 CALCULATIONS- SECTION 304.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER