| 2019-04-09 10:51:19 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020956 |
| | 4/9/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BACH AMENDMENTS TO THE FBC SIXTH EDITION |
| | 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | PLEASE REVIEW THE COMMENTS LISTED BELOW AND RESUBMIT |
| | CORRECTED PLANS |
| | |
| | 1) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR |
| | THE KITCHEN EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, |
| | AND THE WALK-IN FREEZERS- SECTION 107.2.1 WPB. |
| | |
| | 2) PROVIDE A KITCHEN EQUIPMENT PLAN AND EQUIPMENT |
| | SCHEDULE- SECTION 107.2.1 WPB. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL |
| | GAS-FIRED COOKING APPLIANCES AND THE GAS WATER HEATERS- |
| | SECTIONS 623.1 & 624.1 FBC FG. |
| | |
| | 4) SHEET M2.0: PROVIDE COMBUSTION AIR CALCULATIONS FOR |
| | THE COOKING APPLIANCES- SECTION 304.1 FBC FG. |
| | |
| | 5) M1.1: THE COMBUSTION AIR INTAKES FOR THE GAS WATER |
| | HEATERS APPEAR TO BE IN PROXIMITY OF THE EXHAUST OUTLET |
| | FOR KEF-1. PLEASE PROVIDE CLEARANCE DISTANCE |
| | MEASUREMENTS PER THE MANUFACTURER'S INSTALLATION |
| | GUIDELINES- SECTION 303.1 FBC FG. |
| | |
| | 6) M2.0: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR |
| | THE CHEMICAL AND CLEANING STORAGE, TRASH, LAUNDRY, AND |
| | LOCKER ROOMS- TABLE 403.3.1.1 FBC M. PROVIDE A SEQUENCE |
| | OF OPERATION FOR THE FANS- SECTION 501.4 FBC M. |
| | |
| | 7) M1.1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | DRYER, AND PROVIDE A DRYER EXHAUST DIAGRAM SHOWING THE |
| | TOTAL RUN LENGTH OF THE DUCT FROM THE DRYER OUTLET TO |
| | THE TERMINATION LOCATION- SECTIONS 504.1 AND 504.8.4 |
| | FBC M. PLEASE NOTE THAT MAKEUP AIR IS REQUIRED FOR |
| | DRYERS EXHAUSTING MORE THAN 200 CFMS- SECTION 504.6 FBC |
| | M |
| | |
| | 8) M1.1: PROVIDE DUCT SMOKE DETECTORS IN THE SUPPLY |
| | SYSTEMS OF AHU-1 & 2- SECTION 606.2.1 FBC M. |
| | |
| | 9) M1.1: ALTHOUGH KEF-1 & 2 ARE UNDER SEPARATE PERMIT, |
| | PLEASE VERIFY EXHAUST OUTLET CLEARANCE DISTANCES IN |
| | ACCORDANCE WITH SECTIONS 506.3.13.2 & 506.3.13.3 FBC M |
| | LISTED BELOW. |
| | |
| | 506.3.13.2 TERMINATION THROUGH AN EXTERIOR WALL. |
| | EXHAUST OUTLETS SHALL BE PERMITTED TO TERMINATE THROUGH |
| | EXTERIOR WALLS WHERE THE SMOKE, GREASE, GASES, VAPORS |
| | AND ODORS IN THE DISCHARGE FROM SUCH TERMINATIONS DO |
| | NOT CREATE A PUBLIC NUISANCE OR A FIRE HAZARD. SUCH |
| | TERMINATIONS SHALL NOT BE LOCATED WHERE PROTECTED |
| | OPENINGS ARE REQUIRED BY THE FLORIDA BUILDING CODE, |
| | BUILDING. OTHER EXTERIOR OPENINGS SHALL NOT BE LOCATED |
| | WITHIN 3 FEET (914 MM) OF SUCH TERMINATIONS. |
| | |
| | 506.3.13.3 TERMINATION LOCATION. |
| | EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET |
| | (3048 MM) HORIZONTALLY FROM PARTS OF THE SAME OR |
| | CONTIGUOUS BUILDINGS, ADJACENT BUILDINGS AND ADJACENT |
| | PROPERTY LINES AND SHALL BE LOCATED NOT LESS THAN 10 |
| | FEET (3048 MM) ABOVE THE ADJOINING GRADE LEVEL. EXHAUST |
| | OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 |
| | MM) HORIZONTALLY FROM OR NOT LESS THAN 3 FEET (914 MM) |
| | ABOVE AIR INTAKE OPENINGS INTO ANY BUILDING. |
| | |
| | 10) COMMISSIONING OF THE MECHANICAL SYSTEMS ARE |
| | REQUIRED IN ACCORDANCE WITH SECTION C408.2 FBC EC. |
| | MECHANICAL SYSTEMS AND SERVICE WATER-HEATING SYSTEMS |
| | COMMISSIONING AND COMPLETION REQUIREMENTS. |
| | PRIOR TO THE FINAL MECHANICAL AND PLUMBING INSPECTIONS, |
| | THE LICENSED DESIGN PROFESSIONAL, ELECTRICAL ENGINEER, |
| | MECHANICAL ENGINEER OR APPROVED AGENCY SHALL PROVIDE |
| | EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING AND |
| | COMPLETION IN ACCORDANCE WITH THE PROVISIONS OF THIS |
| | SECTION. |
| | REFER TO SECTION C408.2.1 AND PROVIDE A COMMISSIONING |
| | PLAN. |
| | |
| | 11) GENERATOR: A) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND THE UL CERTIFICATE OF COMPLIANCE- SECTION 915.1 FBC |
| | M. B) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | EXHAUST PIPE AND PROVIDE A DIAGRAM SHOWING THE PIPE RUN |
| | FROM THE GENERATOR TO TERMINATION LOCATION ABOVE THE |
| | ROOF. C) PROVIDE ENGINEERED DETAILS SHOWING HOW THE |
| | PIPE WILL BE SUPPORTED AND ATTACHED TO THE BUILDING- |
| | SECTION 301.15 FBC M. D) PROVIDE BACKPRESSURE |
| | CALCULATIONS- SECTION 304.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |