2019-04-02 14:09:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 NFPA 96
  
 1ST REVIEW
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS
  
 GAS COMMENTS: DENIED
 1. SYSTEM SIZED PER FBC FG TABLE 402.4(2). TOTAL LENGTH
 IS 101?. BASED UPON 125? IN THE TABLE, ITEMS C, D AND F
 ARE UNDERSIZED. CORRECT AS REQUIRED BY THE TABLE PER
 WPB FBC 107.2.1
 2. 34? INCREMENT UPSTREAM OF 1ST BRANCH IS SIZED
 2-1/2?. CORRECT SIZE TO COMPLY WITH FBC FG TABLE
 402.4(2) BASED ON 125?.
 3. 5? INCREMENT BETWEEN ITEMS G AND G IS UNDERSIZED.
 CORRECT SIZE TO COMPLY WITH FBC FG TABLE 402.4(2) BASED
 ON 125?.
 4. BRANCH TO WATER HEATERS IS UNDERSIZED. CORRECT SIZE
 TO COMPLY WITH FBC FG TABLE 402.4(2) BASED ON 125?.
 INDIVIDUAL SUPPLY LINE TO EACH OF THE HEATERS IS
 UNDERSIZED. CORRECT SIZES TO COMPLY WITH FBC FG TABLE
 402.4(2) BASED ON 125?.
 5. PER WPB FBC 107.2.1, PROVIDE CUT LENGTHS FOR THE
 HORIZONTAL EAST-WEST INCREMENTS BETWEEN THE WATER
 HEATERS AND THE HORIZONTAL NORTH-SOUTH INCREMENTS TO
 THE VERTICAL DROPS.
 6. PER WPB FBC 107.2.1, SPEC MANUFACTURER MODEL NUMBER
 OF AUTOMATIC GAS SHUT OFF VALVE; PROVIDE WITH MANUAL
 RESET PER NFPA 96 CHAPTER 10.
 7. PER WPB FBC 107.2.1, PROVIDE DETAILS FOR THE
 FOLLOWING SHOWING VALVES, DIRT LEGS, UNIONS AND OTHER
 REQUIRED APPURTENANCES AS REQUIRED BY FBC FG AND NFPA
 96, THE FOLLOWING.
 A. TYPICAL CONNECTION TO COOKING APPLIANCE
 B. CONNECTION TO PUBLIC METER/REGULATOR
 C. EMERGENCY SHUTOFF FOR KITCHEN EQUIPMENT
 8. WILL ALL PIPING BE THREADED, OR WILL SOME BE WELDED?
 PER WPB FBC 107.2.1, PLEASE CLARIFY AND PROVIDE
 SPECIFICATIONS FOR PIPE, VALVES AND FITTINGS.IF WELDING
 IS TO BE REQUIRED, PROVIDE REQUIRED PROCEDURES.
 9. GAS RISER DIAGRAM ON P3.1 INDICATES THREE (3) GAS
 WATER HEATERS. DETAIL ON P5.0 AND PLUMBING FIXTURE
 SCHEDULE ON P4.0 INDICATE TWO (2) GAS WATER HEATERS AND
 ONE (1) ELECTRIC WATER HEATER. PLEASE CLARIFY PER WPB
 FBC 107.2.1.
 10. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 COOKING LINE APPLIANCES PER FBC FG 304.1.
 11. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT (KITCHEN
 EQUIPMENT AND WATER HEATERS) TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC FG 402.2. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION.
 12. PER WPB FBC 107.2.1, SUBMIT A DETAIL SHOWING THE
 TYPE, LOCATION, ELEVATIONS, SIZE, AND TERMINATION
 POINTS OF GAS WATER HEATER DIRECT VENT COMBUSTION AIR
 AND VENT.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  