| Plan Review Notes For Permit 19020956 |
| Permit Number |
19020956 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-05 09:25:26 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) FIRE LINE UNDERGROUND IS INDICATED. ALL FIRE LINE | | | UNDEERGROUND SHALL BE UNDER SEPARATE SHOP DRAWINGS AND | | | PERMIT. | | | | | | ALL FIRE LINE UNDERGROUND SHALL COMPLY WITH NFPA 24. | | | | | | | | | | | | 2) THE HOOD AND SUPPRESSION SYSTEMS SHALL BE UNDER | | | SEPARATE SHOP DRAWINGS AND PERMITS. | | | | | | | | | | | | | | | 3) THERE IS AN INDICATION OF AN EMERGENCY GENERATOR. | | | THE GENERATOR SHALL BE INSTALLED UNDER SEPARATE SHOP | | | DRAWINGS AND PERMIT. | | | | | | THE GENERATOR INSTALLATION SHALL COMPLY WITH NFPA 37, | | | 2015 ED AND 110, 2013 ED. | | | | | | | | | | | | | | | 4) THERE IS AN INDICATION OF NFPA 101, 2018 ED. FOR | | | INFORMATIONAL PURPOSES THE CURRENT EDITION OF NFPA 101 | | | IS 2015. | | | | | | THE CURRENT EDITION OF THE FFPC WAS ADOPED ON DEC. 31, | | | 2018, WHICH INCLUDED NFPA 1, 2015 ED AND 101, 2015 ED | | | WITH FL ADMENDMENTS. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|