Plan Review Notes
Plan Review Notes For Permit 19020956
Permit Number 19020956
Review Stop B
Sequence Number 1
Notes
Date Text
2019-04-01 13:08:202017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020956
 ADD: 4257 UP THE GROVE LANE
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-694-3828
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: MON. APRIL 1ST/ 2019
 ACTION: DENIED
  
 1) ART IN PUBLIC PLACES.
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
  
  
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2) IN THE SUPPORTING DOCUMENT FILE THE REPORT
 COMPUTATIONS FOR FPL WEST PALM BEACH COMMISSARY
 BUILDING DO NOT HAVE AN ELECTRONIC SEAL.
  
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 3) SHEET 040_S-1.0 THE GENERAL NOTES- FOUNDATIONS
 INDICATES THAT A SOILS REPORT HAS BEEN PREPARED.
 SOILS REPORT BY INTERTEK OF 08-24-2018. PLEASE SUBMIT
 EITHER A REPORT WITH ELECTRONIC SIGNATURE OR PAPER
 ORIGINAL WITH ORIGINAL SEAL, SIGNATURE AND DATE.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 4) THE PLANS INDICATE THIS PROPOSED BUILDING WILL HAVE
 TILT-WALL CONSTRUCTION. THIS BUILDING WILL REQUIRE A
 RESIDENT INSPECTOR IN ACCORDANCE WITH SECTION 110.3.9
 OF THE WEST PALM BEACH ADMINISTRATIVE CODE. THE
 BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY
 OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE
 MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED
 INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION
 HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND
 RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION
 OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH
 REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY
 A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING
 OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION
 SERVICE IN THE FOLLOWING INSTANCES:
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION (TILT-WALL BUILDINGS)
  
 RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL PARTIES
 NOTARIZED AND RETURNED TO THE BUILDING DEPARTMENT.
 FORMS SENT TO: [email protected] TIME: 10:37 AM MON.
 APRIL 01/ 2019
  
 5A) SHEET 040_S-1.0 UNDER THE HEADING OF DEFERRED
 SUBMITTALS INDICATES THE CONCRETE TILT PANEL ERECTION
 IS TO BE DEFERRED. THE RESIDENT INSPECTOR WILL HAVE TO
 HAVE THE INFORMATION LISTED UNDER TILT-UP PANELS,
 PANEL MINIMUM MODULES OF RUPTURE AND COMPRESSIVE
 STRENGTH AS REQUIRED BY THE LIFTING ENGINEER, LIFTING
 INSERTS AND ADDITIONAL REINFORCING STEEL, CHAIRS & OR
 BOLSTERS AS REQUIRED BY THE SPECIALTY ENGINEER,
 LOCATION OF THE REINFORCEMENT FOR THE TILT WALL PANEL,
 ALL EMBEDS (I.E. PLATES, ANGLES, ETC.) LOCATION OF ALL
 OPENINGS AND THE CORRESPONDING DIMENSIONS, MISC.
 OPENINGS FOR REQUIRED, FIRE LINES, PLUMBING, ELECTRICAL
 LINES BEFORE THE CONCRETE PANELS CAN BE POURED.
  
 5B) 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 5C) THE RESIDENT INSPECTOR WILL BE REQUIRED TO OVERSEE
 ALL STRUCTURAL INSPECTIONS AS REQUIRED IN THE CITY
 ADMINISTRATIVE CODE 100.3 FOUNDATION THROUGH THE
 ANCHORING OF THE ROOF DECK WITH EXCEPTION OF COMPONENTS
 AND CLADDING OF WINDOWS, DOORS AND ROOFING, THESE WILL
 BE COMPLETED BY THE CITY BUILDING INSPECTORS. IF THERE
 IS ANY QUESTIONS AS TO WHAT THE RESIDENT INSPECTOR WILL
 NEED TO VERIFY AS TO STRUCTURAL INSPECTIONS PLEASE
 CONTACT KEN CONRAD ADMINISTRATOR OF THE RESIDENT AND
 SPECIAL INSPECTOR PROGRAM AT:
 KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 6) THE STRUCTURAL SHEETS HAVE THE ELECTRONIC SIGNATURES
 100% COMPLETE, WE ARE GETTING THE NOTE,
 THE SIGNER?S IDENTITY IS UNKNOWN BECAUSE IT HAS NOT
 BEEN INCLUDED IN YOUR LIST OF TRUSTED CERTIFICATES AND
 NONE OF ITS PARENT CERTIFICATES ARE TRUSTED
 CERTIFICATES. THE ARCHITECTURAL SHEETS OK. 61G15-23.005
 PROCEDURES FOR SIGNING AND SEALING ELECTRONICALLY
 TRANSMITTED PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
  
 7) SHEET 038_A-5 WINDOW SECTION 4 SHOWS 1 INCH WOOD
 WINDOW BUCKS. THE PLAN INDICATES THE USE OF MASONRY
 ANCHORS. NONE OF THE ARCHITECTURAL NOR STRUCTURAL
 SHEETS SHOW ANY MORE DETAIL OF THE TYPES OF ANCHORS TO
 BE INSTALLED, SIZE AND DIAMETER OR SPACING OF THE
 ANCHORS FROM THE BUCKS TO THE CONCRETE TILT WALL. THE
 ANCHORING OF WOOD BUCKS IS NORMALLY THE STRUCTURAL
 ENGINEERS? RESPONSIBILITY AND NOT FOUND IN THE PRODUCT
 APPROVALS.
 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS
 SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 8) SHEET 029_A-3.3 RESTROOM ELEVATIONS DETAIL THE HC
 SINK SHOWS THE 40 INCH MEASUREMENT OF 40 INCHES FROM
 THE FINISH FLOOR TO THE BOTTOM OF THE MIRROR. PLEASE
 REVIEW THE 2017 FBC-ACCESS. CODE SECTION
 603.3 MIRRORS. MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES (1015 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED
 ABOVE LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH
 THE BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES
 (890 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 9) SHEET 030_A3.4 THE SECTION OF THE LAUNDRY ROOM SINK
 SHOWS THE ELEVATION OF 2 FOOT 10 INCHES TO THE TOP OF
 THE COUNTERTOP BUT NOT THE TOP OF THE SINK, THE
 THICKNESS OF THE SINK RIM MAY OR MAY NOT BE IN THE
 CONSTRUCTION TOLERANCES THIS WOULD BE SOMETHING THE
 PLUMBING INSPECTOR AND OR PLUMBING REVIEWER MAY NEED TO
 ADDRESS.
  
 DISCREPANCY IN PLANS, SHEET 036_A-4.2 DETAIL J SHOWS
 THE ROOF AS SBS HEAT WELDED MODIFIED BITUMINOUS
 MEMBRANE ROOFING W/ CAP SHEET OVER GYPSUM FIBER BOARD
 AND POLYSOCYANURATE ROOF INSULATION AND B DECK WHEREAS
 THE STRUCTURAL SHEET 043_S3.1 DETAIL B SHOWS A 4 INCH
 CONCRETE SLAB ON B DECK. PLEASE ALSO REFER BACK TO THE
 INPUT DATA REPORT WHICH ALSO HAS DIFFERENT MATERIALS
 AND THICKNESS. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 10) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS.
 (C) PANEL WALLS: WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION ROOFING MATERIALS,
  
 11A) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 11C) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 12) IDENTIFY GLAZING. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 13) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION
  
 14) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 15) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 16) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER19030471
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  