Plan Review Notes
Plan Review Notes For Permit 19020934
Permit Number 19020934
Review Stop E
Sequence Number 4
Notes
Date Text
2019-06-14 08:26:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND
 INDIVIDUAL PANELS, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. RISER SHOWS
 TWO 200 AMP METERS TO UNITS, WHERE ARE THE LOADS FOR
 THESE? NEW 100 AMP PANEL B SHOWS A NEW RTU, BUT ONLY
 THE BLOWER MOTOR LOAD IS INCLUDED. THE LARGER OF AC OR
 HEAT LOAD SHOULD BE INCLUDED IN THIS PANEL LOAD.
 PROVIDE SPEC SHEET FOR NEW RTU WITH ELECTRICAL
 REQUIREMENTS. NEC 110.3, 215.2, 220, 220.60, 408.30;
 WPB FBC 107.2.1 (4TH REVIEW, STILL NOT CLARIFIED OR
 CORRECTED. LOAD CALCULATION FOR 600 AMP MAIN NOT
 PROVIDED. ADDITIONALLY, THE PANEL SCHEDULE SHOWS
 CIRCUITS A-21, A-23, A-25, AND A-27 AS SPARES. WHY IS
 THERE NO LOAD INCLUDED FOR THESE STYLING STATIONS? THIS
 WOULD NOT BE CALCULATED AT 180 VA PER RECEPTACLE AS
 THIS IS FOR A SPECIFIC LOAD. ALSO, THERE IS NOT LOAD
 INCLUDED FOR THE EXHAUST FANS SHOWN ON THE MECHANICAL
 PLAN. NEC 220, 220.14(A) PROVIDE CLARIFICATION AND
 CORRECTIONS.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved