| 2019-06-14 08:26:20 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND |
| | INDIVIDUAL PANELS, INCLUDE EXISTING AND NEW LOADS TO |
| | CONFIRM CAPACITY OF SERVICE IS ADEQUATE. RISER SHOWS |
| | TWO 200 AMP METERS TO UNITS, WHERE ARE THE LOADS FOR |
| | THESE? NEW 100 AMP PANEL B SHOWS A NEW RTU, BUT ONLY |
| | THE BLOWER MOTOR LOAD IS INCLUDED. THE LARGER OF AC OR |
| | HEAT LOAD SHOULD BE INCLUDED IN THIS PANEL LOAD. |
| | PROVIDE SPEC SHEET FOR NEW RTU WITH ELECTRICAL |
| | REQUIREMENTS. NEC 110.3, 215.2, 220, 220.60, 408.30; |
| | WPB FBC 107.2.1 (4TH REVIEW, STILL NOT CLARIFIED OR |
| | CORRECTED. LOAD CALCULATION FOR 600 AMP MAIN NOT |
| | PROVIDED. ADDITIONALLY, THE PANEL SCHEDULE SHOWS |
| | CIRCUITS A-21, A-23, A-25, AND A-27 AS SPARES. WHY IS |
| | THERE NO LOAD INCLUDED FOR THESE STYLING STATIONS? THIS |
| | WOULD NOT BE CALCULATED AT 180 VA PER RECEPTACLE AS |
| | THIS IS FOR A SPECIFIC LOAD. ALSO, THERE IS NOT LOAD |
| | INCLUDED FOR THE EXHAUST FANS SHOWN ON THE MECHANICAL |
| | PLAN. NEC 220, 220.14(A) PROVIDE CLARIFICATION AND |
| | CORRECTIONS.) |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |