Plan Review Notes
Plan Review Notes For Permit 19020934
Permit Number 19020934
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-29 11:55:23PLUMBING 1ST REVIEW**DENIED**
  
 ***FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF
 DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT
 FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH
 THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
  
 1) 2ND REQUEST** PLAN DOES NOT SHOW THE REQUIRED HI-LO
 DRINKING FOUNTAIN AS REQUIRED IN FBC-P 410.3. THE
 BOTTLE WATER DISPENCER'S SHOWN IS ONLY ALLOWED TO
 REPLACED UP TO 50% OF THE REQUIRED NUMBER OF DRINKING
 FOUNTAINS REQUIRED. FBC-P 410.4
  
 2) 2ND REQUEST SHT.2.1 UNDER TOILET ACCESSORY SCHEDULE
 HAS SOME INCORRECT INFORMATION FOR THE GRAB BARS. SHOW
 GRAB BAR HEIGHT AS 33"-36" TO THE TOP OF GRIPPING
 SURFACE. GB CALLS OUT 33" TO THE CENTER BUT GB1 CALLS
 OUT 33"-36" TO THE CENTER WHICH IF MOUNTED @ 36" WOULD
 HAVE THE GRIPPING SURFACE TO HIGH. FBC-ACC 609.4
  
 3) ANSWERED
  
 4) 2ND REQUEST PROVIDE THE MANUFACTURE INSTALLATION
 MANUAL FOR THE GAS TANKLESS WATER HEATER. WHICH
 MODEL.FBC 107.3.5
  
 5) 2ND REQUEST PROVIDE THE MANUFACTURES INSTALLATION
 MAUNAL SHOWING THE HAIR WAS STATIONS COMPLY WITH
 FBC-P423.3. SHOW AS TEMP LIMITED BY A ASSE 1070 DEVICE.
  
 6) 2ND REQUEST PROVIDE A SEPERATE SIZED WATER ISOMETRIC
 DRAWNING WITH PIPE SIZING. FBC 107.3.5
  
 7) 2ND REQUESTSHT 5.1 WASHING MACHINE DETAIL CALLS OUT
 3" PIPING TO WASHING MACHINE BOX BUT NOTE TOP CENTER
 SAAYS PROPOSED WASHING WITH 2" PVC. PLEASE CLEARIFY.
 FBC 107.3.5
  
 8) NEW COMMENT: PROVIDE A LINT INTERCEPTOR FOR THE
 WASHING MACHINE. PROVIDE COMPLETE INSTALLATION MANUALS
 AND REVISE SANITARY ISOMETRIC DRAWING. FBC 1003.1,
 1003.2, 1003.6
  
  
 PLEASE PROVIDE A NARRATIVE REAPONSE TO ALL COMMENTS. I
 WOULD RECOMMENDED A MEETING WITH PLAN REVIEW STAFF
 BEFORE RESUBMITTING .
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  