| 2019-04-29 11:55:23 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | ***FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF |
| | DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT |
| | FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH |
| | THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| | REVIEW. |
| | |
| | |
| | 1) 2ND REQUEST** PLAN DOES NOT SHOW THE REQUIRED HI-LO |
| | DRINKING FOUNTAIN AS REQUIRED IN FBC-P 410.3. THE |
| | BOTTLE WATER DISPENCER'S SHOWN IS ONLY ALLOWED TO |
| | REPLACED UP TO 50% OF THE REQUIRED NUMBER OF DRINKING |
| | FOUNTAINS REQUIRED. FBC-P 410.4 |
| | |
| | 2) 2ND REQUEST SHT.2.1 UNDER TOILET ACCESSORY SCHEDULE |
| | HAS SOME INCORRECT INFORMATION FOR THE GRAB BARS. SHOW |
| | GRAB BAR HEIGHT AS 33"-36" TO THE TOP OF GRIPPING |
| | SURFACE. GB CALLS OUT 33" TO THE CENTER BUT GB1 CALLS |
| | OUT 33"-36" TO THE CENTER WHICH IF MOUNTED @ 36" WOULD |
| | HAVE THE GRIPPING SURFACE TO HIGH. FBC-ACC 609.4 |
| | |
| | 3) ANSWERED |
| | |
| | 4) 2ND REQUEST PROVIDE THE MANUFACTURE INSTALLATION |
| | MANUAL FOR THE GAS TANKLESS WATER HEATER. WHICH |
| | MODEL.FBC 107.3.5 |
| | |
| | 5) 2ND REQUEST PROVIDE THE MANUFACTURES INSTALLATION |
| | MAUNAL SHOWING THE HAIR WAS STATIONS COMPLY WITH |
| | FBC-P423.3. SHOW AS TEMP LIMITED BY A ASSE 1070 DEVICE. |
| | |
| | 6) 2ND REQUEST PROVIDE A SEPERATE SIZED WATER ISOMETRIC |
| | DRAWNING WITH PIPE SIZING. FBC 107.3.5 |
| | |
| | 7) 2ND REQUESTSHT 5.1 WASHING MACHINE DETAIL CALLS OUT |
| | 3" PIPING TO WASHING MACHINE BOX BUT NOTE TOP CENTER |
| | SAAYS PROPOSED WASHING WITH 2" PVC. PLEASE CLEARIFY. |
| | FBC 107.3.5 |
| | |
| | 8) NEW COMMENT: PROVIDE A LINT INTERCEPTOR FOR THE |
| | WASHING MACHINE. PROVIDE COMPLETE INSTALLATION MANUALS |
| | AND REVISE SANITARY ISOMETRIC DRAWING. FBC 1003.1, |
| | 1003.2, 1003.6 |
| | |
| | |
| | PLEASE PROVIDE A NARRATIVE REAPONSE TO ALL COMMENTS. I |
| | WOULD RECOMMENDED A MEETING WITH PLAN REVIEW STAFF |
| | BEFORE RESUBMITTING . |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |
| | |