Plan Review Notes
Plan Review Notes For Permit 19020934
Permit Number 19020934
Review Stop M
Sequence Number 2
Notes
Date Text
2019-05-02 16:29:422ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19020934
 5/2/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED SUBMITTED MECHANICAL PLAN SHOWS THESE
 PRIOR AND NEW DEFICIENCIES:
  
 A) THE REQUESTED EXHAUST VENTILATION CALCULATIONS WERE
 NOT PROVIDED- SEE COMMENT #1 FROM THE 1ST REVIEW
 PRINTED HERE- 1) SHEET 4.1: EF-2 AT 150 CFMS APPEARS TO
 BE UNDERSIZED FOR THE REQUIRED EXHAUST RATE OF 0.60
 CFMS PER SF. FOR THE SALON AREA- SEE TABLE 403.3.1.1
 AND PROVIDE CALCULATIONS.
  
 B) NO EXHAUST HAS BEEN PROVIDED FOR THE TREATMENT ROOM-
 TABLE 403.3.1.1 FBC M.
  
 C) NO OUTSIDE AIR DUCT OR AUTOMATIC CONTROL DAMPER HAVE
 BEEN PROVIDED FOR THE NEW 5-TON AC SYSTEM- TABLE
 403.3.1.1 FBC M & SECTION C403.2.4.3 FBC EC.
  
 D) CLARIFY THE LOCATION OF THE NEW 5-TON CONDENSER. IS
 THE UNIT TO BE GROUND MOUNTED OR WALL BRACKET MOUNTED?
 THE WALL BRACKET DETAIL SHOWN IS FOR A PACKAGE UNIT. IN
 EITHER CASE- WALL OR GROUND- COMPLETE ENGINEERING IS
 REQUIRED- SECTION 301.15 FBC M. PLEASE NOTE THAT THE
 CONDENSER BELOW THE SLOPING ROOF MAY BE DETRIMENTAL TO
 THE FUNCTION OF THE SYSTEM AND MAY BE
  
 INCONSISTENT WITH THE MANUFACTURER'S INSTALLATION AND
 WARRANTY GUIDELINES. SUBMIT DOCUMENTATION VERIFYING
 COMPLIANCE- SEE SECTION 304.1 FBC M.
  
 E) THE NEW ENERGYGAUGE COMPLIANCE REPORT INDICATES THE
 NEW 5-TON SYSTEM IS 17 SEER, HOWEVER THE SCHEDULE ON
 THE PLAN INDICATES 14 SEER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  