| 2019-04-29 10:52:34 | GAS 2ND REVIEW**DENIED** |
| | |
| | |
| | *FL ST 553.80 (B)2B WITH RESPECT TO EVALUATION OF |
| | DESIGN PROFESSIONALS? DOCUMENTS, IF A LOCAL GOVERNMENT |
| | FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH |
| | THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT |
| | DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE |
| | TIMES FOR FAILURE TO CORRECT A CODE VIOLATION |
| | SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION, |
| | INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION, |
| | STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING, |
| | VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS |
| | SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF |
| | THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO |
| | CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH |
| | TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED |
| | FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT |
| | OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS |
| | REVIEW. |
| | |
| | |
| | |
| | 1) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 |
| | |
| | 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) |
| | |
| | 3) 2ND REQUEST**SUBMIT TWO COPIES OF THE APPLICABLE |
| | SIZING TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A |
| | NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING |
| | TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE |
| | USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE |
| | 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES |
| | 402.4 (1) THRU 402.4 (37) |
| | |
| | 4) 2ND REQUEST**GAS TANKLESS CALLED OUT ON SHT.5.1 AS |
| | 140,000 BTU'S. INSTALLATION MANUAL PROVIDE DOES NOT |
| | LIST A MODEL WITH THAT BTU RATING. PLEASE CLARIFY AND |
| | CALL OUT MODEL OF TANKLESS BEING USED. FBC 107.2.1 |
| | |
| | 5) 2ND REQUEST**DRYER SPEC SUBMITTED DOES NOT SHOW |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, |
| | |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |