| 2019-05-15 10:47:32 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND |
| | INDIVIDUAL PANELS, INCLUDE EXISTING AND NEW LOADS TO |
| | CONFIRM CAPACITY OF SERVICE IS ADEQUATE. RISER SHOWS |
| | TWO 200 AMP METERS TO UNITS, WHERE ARE THE LOADS FOR |
| | THESE? NEW 100 AMP PANEL B SHOWS A NEW RTU, BUT ONLY |
| | THE BLOWER MOTOR LOAD IS INCLUDED. THE LARGER OF AC OR |
| | HEAT LOAD SHOULD BE INCLUDED IN THIS PANEL LOAD. |
| | PROVIDE SPEC SHEET FOR NEW RTU WITH ELECTRICAL |
| | REQUIREMENTS. NEC 110.3, 215.2, 220, 220.60, 408.30; |
| | WPB FBC 107.2.1 (INFORMATION NOT CLARIFIED. ARE THERE |
| | TWO 200 AMP METERS FEEDING OTHER LOADS TO UNIT 7 AND 8, |
| | WHERE ARE THE METERS FOR THE 100 AMP SINGLE PHASE |
| | PANELS, AND WHAT IS THE LOAD OF THE 600 AMP MAIN? ALSO, |
| | WHEN LOADS STATED ARE ADDED TOGETHER, THE AMOUNT IS |
| | DIFFERENT THAN WHAT IS STATED FOR A PHASE OF EACH |
| | PANEL. THE CORRECTED MATH SHOWS THE PANEL AND FEEDERS |
| | AS OVERLOADED. PROVIDE CLARIFICATIONS AND CORRECTIONS.) |
| | 2. PROVIDE LOCATION OF ALL PANELS IN UNITS. PROVIDE |
| | PANEL SCHEDULES FOR ALL PANELS INDICATING ANY NEW OR |
| | ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| | CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| | TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, |
| | 215.5, 408.4 (NO REPLY TO THIS COMMENT.) |
| | 3. SHOW WINDOW RECEPTACLES ARE SHOWN ON PANEL SCHEDULE, |
| | BUT NOT SHOWN ON PLAN. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1; NEC 210.62 (COMMENT NOT ADDRESSED. PROVIDE |
| | SHOW WINDOW OUTLETS PER CODE.) |
| | 4. ALL RECEPTACLES WITHIN 6 FEET OF A SINK MUST BE GFCI |
| | PROTECTED. PROVIDE CORRECTION. NEC 210.8 (RECEPTACLE |
| | OOUTLET ADJACENT TO HAIR WASH AREA NOT CORRECTED.) |
| | 5. CORRECTED. |
| | 6. PROVIDE COPY OF CONTRACT TO VERIFY VALUE OF WORK FOR |
| | TOTAL PROJECT. WPB FBC 109.3 (NOT PROVIDED.) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |