| 2019-05-14 16:23:10 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19020934 |
| | ADD: 3030 S DIXIE SUITES 7 & 8 |
| | CONT: TEKONICA INDUSTRIES INC. |
| | TEL: 561-745-2858 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: 5/14/2019 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2A) COMPLIED. |
| | |
| | 2B) COMPLIED. |
| | |
| | 2C) COMPLIED |
| | |
| | 3A) PARTIALLY COMPLIED. SUBMIT PRODUCT APPROVALS OR |
| | ENGINEERING FOR THE A/C WALL BRACKET. THE INFORMATION |
| | THAT WAS SUBMITTED IS NOT A PRODUCT APPROVAL. SHEET 1.1 |
| | INDICATES THE REMOVAL AND REPLACEMENT OF BRACKET FOR |
| | WALL HUNG A/C CONDENSER. SHEET 4.1 DETAIL FOR WALL |
| | BRACKET INDICATES THE INSTALLATION OF A MIAMI TECH WALL |
| | BRACKET SYSTEM, PLEASE PROVIDE THE PRODUCT APPROVAL OR |
| | ENGINEERING FOR THIS BRACKET AND ANCHOR OF THE |
| | CONDENSER TO THE WALL BRACKET. |
| | 2017 FBC-B 1609.1.2 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(C) WALL LOUVERS, OR OTHER PRODUCTS TESTED IN |
| | REGARDS TO NEW TECHNOLOGY |
| | |
| | 3B) COMPLIED. |
| | |
| | 3C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. FBC-B-1609.6.4.4.1 COMPONENTS |
| | AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR |
| | CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES |
| | COMPONENTS AND ATTACHMENTS. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 6) NEW COMMENT. THE LIFE SAFETY PLAN, SHEET 3.1, IS |
| | MISSING FROM THE PLAN SETS. FBC 107.2.1 |
| | |
| | ROBERT MCDOUGAL |
| | COMMERCIAL COMBINATION PLANS EXAMINER |