| Date |
Text |
| 2019-03-13 12:29:09 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | PLAN REVIEW WAS BASED ON THIS BEING A LEVEL LLL |
| | RENOVATION COMPLYING WITH THE FBC 2017 6TH ED. |
| | |
| | 1) PLAN DOES NOT SHOW THE REQUIRED HI-LO DRINKING |
| | FOUNTAIN AS REQUIRED IN FBC-P 410.3. THE BOTTLE WATER |
| | DISPENCER SHOWN IS ONLY ALLOWED TO REPLACED UP TO 50% |
| | OF THE REQUIRED NUMBER OF DRINKING FOUNTAINS REQUIRED. |
| | FBC-P 410.4 |
| | |
| | 2) SHT.2.1 UNDER TOILET ACCESSORY SCHEDULE HAS SOME |
| | INCORRECT INFORMATION FOR THE GRAB BARS. BEING THAT YOU |
| | HAVE A CORRECT TOILET ROOM ELEVATIONS ON SHT5.1 YOU CAN |
| | REMOVE THE NOTES OR CORRECT AS FOLLOWED. GB-1 (SIDE |
| | BAR) 42" BAR MUST BE MOUNT @ 12" TO GET THE REQUIRED |
| | OVERALL 54".FBC-A 604.5.1 (2B) GB-1 (REAR) 36" GRAB BAR |
| | SHALL BE MOUNT 12" FOR CENTER OF TOILET BEING THAT THE |
| | TOILET IS PERMITTED TO BE 16"-18" IT CAN BE 4'-6' FROM |
| | THE SIDE WALL. FBC-A 604.5.2 |
| | |
| | 3) THE EMPLOYEE BREAKROOM SINK SHALL COMPLY WITH |
| | FLORIDA ACCESSIBILITY CHAPTER 6 SAME AS THE WAITING |
| | ROOM DOES. PLEASE PROVIDE CLEAR FLOOR SPACE AND SHOW |
| | CABINET HEIGHT DETAIL LISTING MAX 34".FBC-A 606.2, |
| | 606.3 |
| | |
| | 4) PROVIDE THE MANUFACTURE INSTALLATION MANUAL FOR THE |
| | GAS TANKLESS WATER HEATER. FBC 107.3.5 |
| | |
| | 5) PROVIDE THE MANUFACTURES INSTALLATION MAUNAL SHOWING |
| | THE HAIR WAS STATIONS COMPLY WITH FBC-P423.3 AND ARE |
| | TEMP LIMITED BY A ASSE 1070 DEVICE. |
| | |
| | 6) PROVIDE A SEPERATE SIZED WATER ISOMETRIC DRAWNING. |
| | FBC 107.3.5. IF THE DEVELOPED LENGHT OF THE HOT WATER |
| | LINE IS OVER 50' A RECIRCULATION SYSTEM WAS ALSO BE |
| | INSTALL. FBC-P 607.2 AND INSULATED WITH 1" WALL |
| | COMPLYING WITH FBC-ENERGY C404.6 |
| | |
| | 7) SHT 5.1 WASHING MACHINE DETAIL CALLS OUT 3" PIPING |
| | TO WASHING MACHINE BOX BUT NOTE TOP CENTER SAAYS |
| | PROPOSED WASHING WITH 2" PVC. PLEASE CLEARIFY. FBC |
| | 107.3.5 |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | |
| | SAMANTHA HILL |
| | CHIEF PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |