| 2019-03-19 12:23:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020934 |
| | 3/19/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 4.1: EF-2 AT 150 CFMS APPEARS TO BE UNDERSIZED |
| | FOR THE REQUIRED EXHAUST RATE OF 0.60 CFMS PER SF. FOR |
| | THE SALON AREA- SEE TABLE 403.3.1.1 AND PROVIDE |
| | CALCULATIONS. |
| | |
| | 2) 4.1: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF |
| | DAMPERS FOR THE OUTDOOR AIR INTAKES ON THE RTU'S - |
| | SECTION C403.2.4.3 FBC-17 ENERGY CONSERVATION. |
| | |
| | 3) 4.1: THE LOCATIONS OF THE RTU'S AND DUCT TRUNKS |
| | BELOW THE SLOPING ROOF MAY BE DETRIMENTAL TO THE |
| | FUNCTION OF THE SYSTEM AND MAY BE INCONSISTENT WITH THE |
| | MANUFACTURER'S INSTALLATION AND WARRANTY GUIDELINES. |
| | SUBMIT DOCUMENTATION VERIFYING COMPLIANCE- SEE SECTION |
| | 304.1 FBC M. |
| | |
| | 4) 4.1: SITE SPECIFIC ENGINEERING IS REQUIRED FOR |
| | INSTALLATION OF THE RTU AND WALL BRACKET- SECTION |
| | 301.15 FBC M. A) PROVIDE THE WIND LOAD DESIGN CRITERIA |
| | PER SECTION 1609 FBC B. B) PROVIDE A FL. PRODUCT |
| | APPROVAL OR MIAMI-DADE NOA FOR THE BRACKET. C) REQUIRED |
| | DETAILS- BRACKET TO WALL ATTACHMENT, AND RTU TO BRACKET |
| | ATTACHEMNT. |
| | |
| | 5) THE SUMMARY AC LOAD CALCULATIONS MUST BE SIGNED AND |
| | SEALED BY A F. LICENSED ENGINEER- SECTION C403.2.1 |
| | EXCEPTION FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |