Plan Review Notes
Plan Review Notes For Permit 19020934
Permit Number 19020934
Review Stop E
Sequence Number 1
Notes
Date Text
2019-03-16 10:50:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND
 INDIVIDUAL PANELS, INCLUDE EXISTING AND NEW LOADS TO
 CONFIRM CAPACITY OF SERVICE IS ADEQUATE. RISER SHOWS
 TWO 200 AMP METERS TO UNITS, WHERE ARE THE LOADS FOR
 THESE? NEW 100 AMP PANEL B SHOWS A NEW RTU, BUT ONLY
 THE BLOWER MOTOR LOAD IS INCLUDED. THE LARGER OF AC OR
 HEAT LOAD SHOULD BE INCLUDED IN THIS PANEL LOAD.
 PROVIDE SPEC SHEET FOR NEW RTU WITH ELECTRICAL
 REQUIREMENTS. NEC 110.3, 215.2, 220, 220.60, 408.30;
 WPB FBC 107.2.1
 2. PROVIDE LOCATION OF ALL PANELS IN UNITS. PROVIDE
 PANEL SCHEDULES FOR ALL PANELS INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4
 3. SHOW WINDOW RECEPTACLES ARE SHOWN ON PANEL SCHEDULE,
 BUT NOT SHOWN ON PLAN. PROVIDE CORRECTION. WPB FBC
 107.2.1; NEC 210.62
 4. ALL RECEPTACLES WITHIN 6 FEET OF A SINK MUST BE GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8
 5. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 6. PROVIDE COPY OF CONTRACT TO VERIFY VALUE OF WORK FOR
 TOTAL PROJECT. WPB FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  