Plan Review Notes
Plan Review Notes For Permit 19020934
Permit Number 19020934
Review Stop B
Sequence Number 1
Notes
Date Text
2019-03-12 11:12:342017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19020934
 ADD: 3030 S DIXIE SUITES 7 & 8
 CONT: TEKONICA INDUSTRIES INC.
 TEL: 561-745-2858
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 12/ 2019
 ACTION: DENIED
  
 1) SHEET 2.1 THE DESIGNER OF RECORD HAS INDICATED THIS
 IS A LEVEL III ALTERATION. PLEASE PROVIDE CODE
 COMPLIANCE WITH THE 2017 EXISTING BUILDING CODE
 SECTION:
 [BS] 907.4.1 EVALUATION AND ANALYSIS. AN ENGINEERING
 EVALUATION AND ANALYSIS THAT ESTABLISHES THE STRUCTURAL
 ADEQUACY OF THE ALTERED STRUCTURE SHALL BE PREPARED BY
 A REGISTERED DESIGN PROFESSIONAL AND SUBMITTED TO THE
 CODE OFFICIAL.
  
 2A) SHEET 2.1 THE DESIGNER OF RECORD HAS NOTED ON THE
 PLANS THE NEW DOOR OPENINGS TO THE EXTERIOR BACK OF THE
 TENANT SPACE ARE TO BE A MIAMI-DADE NOA 17- 17-0426.02.
 SUBMITTED WITH THE DESIGNER OF RECORDS APPROVAL IS NOA
 14-1021.03. PLEASE UPDATE THE NOTE ON SHEET 2.1 TO
 COINCIDE WITH THE APPROVED NOA. 107.2.1.2 ADDITIONAL
 INFORMATION NEEDED.
  
 2B) WITHIN THE APPROVED NOA BY THE DESIGNER OF RECORD
 THERE IS 2 DOOR LOCKING TYPES, A DEADBOLT AND LOCK OR
 PANIC HARDWARE DEVICE, PLEASE EITHER CIRCLE ON THE
 PRODUCT APPROVAL (NOA 17-0426.02) OR INDICATE ON SHEET
 2.1. 1010.1.10 PANIC AND FIRE EXIT HARDWARE.2017 FBC-B.
  
 2C) PLEASE NOTE THERE IS NO WIND DESIGN CRITERIA. 2017
 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3A) SHEET 1.1 INDICATES THE REMOVAL AND REPLACEMENT OF
 BRACKET FOR WALL HUNG A/C CONDENSER. SHEET 4.1 DETAIL
 FOR WALL BRACKET INDICATES THE INSTALLATION OF A MIAMI
 TECH WALL BRACKET SYSTEM, PLEASE PROVIDE THE PRODUCT
 APPROVAL OR ENGINEERING FOR THIS BRACKET AND ANCHOR OF
 THE CONDENSER TO THE WALL BRACKET.
 2017 FBC-B 1609.1.2 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS, OR OTHER PRODUCTS TESTED IN
 REGARDS TO NEW TECHNOLOGY
  
 3B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. FBC-B-1609.6.4.4.1 COMPONENTS
 AND CLADDING. WIND PRESSURE FOR EACH COMPONENT OR
 CLADDING ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES
 COMPONENTS AND ATTACHMENTS.
  
 4) THERE ARE MULTIPLE OF LOOSE SHEETS (1.1, 4.1 & 6.1)
 IN THE PERMIT PACKAGE, PLEASE PROVIDE ADDITIONAL
 INFORMATION ON THESE SHEETS? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  