| Plan Review Notes For Permit 19020927 |
| Permit Number |
19020927 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-18 15:12:43 | PLUMBING 1ST REVIEW PERMIT # 19020927**DENIED** | | | | | | 1) SHT A2 CALLS OUT GRAB BARS TO BE MOUNTED 33"-36" TO | | | THE CENTER LINE OF THE BAR.GRAB BARS SHALL BE INSTALLED | | | IN A HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM | | | AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR | | | MEASURED TO THE TOP OF THE GRIPPING SURFACE FBC-ACC | | | 609.4\ | | | | | | 2) SHOW PAPER DISPENSER 7"-9" FROM THE FRONT OF THE | | | TOILET. FBC-ACC 604.9.6 | | | | | | 3)IS IT YOUR INTENT TO MAKE ALL FIXTURE AND RESTROOMS | | | COMPLY WITH THE FLORIDA ACCESSIBILITY? SHT.T1 UNDER | | | GENERAL NOTES E) CODE NOTES #8 CALLS FOR ALL FIXTURES | | | AND HARDWARE TO COMPLY WITH ADA/ FBC-ACC. FBC 107.2.1 | | | | | | 4) PROVIDE COMPLETE BATHROOM LAY OUT SHOWING CLEAR | | | FLOOR SPACE FOR BOTHT THE TOILET AND SINK COMPLYING | | | WITH FBC-ACC604.3.2, 604.8.1.6 | | | | | | TIM HUNT | | | PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] |
|