| 2019-03-11 15:04:12 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19020927 |
| | ADD: 4100 S DIXIE HWY. SUITE: B |
| | CONT: LEIGHTON MCGINN CO. |
| | TEL: 561-863-4455 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY / MARCH 11/ 2019 |
| | ACTION: DENIED |
| | 1) IT APPEARS THE SUBMITTED PLANS WERE ORIGINALLY PAPER |
| | PLANS THAT WERE CONVERTED TO DIGITAL PLANS, NONE OF THE |
| | DESIGNER OF RECORD SIGNATURE AND SEAL ARE DIGITAL |
| | SIGNATURE AND SEAL. |
| | ARCHITECTS: FLORIDA ADMINISTRATIVE CODE 61G1-16.005. |
| | PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR |
| | ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS. |
| | |
| | 2) SHEET 004_A2 THE WATER CLOSET DETAIL SHOWS THE GRAB |
| | BARS BEING MEASURED FROM THE CENTERLINE OF THE GRAB BAR |
| | TO FINISH FLOOR. PLEASE NOTE UNDER THE 2017 |
| | FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF GRAB |
| | BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE, NOT CENTERLINE. |
| | |
| | 3) SHEET 005_A3 SHOWS AN OPEN SHELF THE BOTTOM AT 56 |
| | INCHES OR 4 FOOT 8 INCHES ABOVE THE FINISH FLOOR, IT |
| | APPEARS TO BE FOR A MICROWAVE. SHEET 006_E1 THE POWER |
| | PLAN SHOWS AN OUTLET AT 72 INCHES FOR A MICROWAVE |
| | MACHINE. WITH A MICROWAVE PLACED IN THIS POSITION |
| | COMPLIANCE CAN NOT BE ACHIEVED FOR CODE SECTIONS, 2017 |
| | FBC-ACCESSIBILITY CODE: |
| | |
| | 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1 |
| | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| | OBSTRUCTED HIGH REACH. |
| | |
| | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL |
| | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL |
| | BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| | GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| | REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS |
| | MAXIMUM. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |