| Plan Review Notes For Permit 19020913 |
| Permit Number |
19020913 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-03-15 10:44:54 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY E.I., BN, PX | | | BUILDING PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | 1. THE WINDOW LOAD CHART IS NOT SIGNED BY THE ENGINEER. | | | PLEASE RE-SUBMIT WITH A VALID DIGITAL SIGNATURE. FBC | | | 107 | | | | | | 2. THE GLASS TYPE INDICATED DO NOT MEET THE WIND LOAD | | | PRESSURE REQUIRED ON THE WIND LOAD CHART. PLEASE HAVE | | | THE ENGINEER SIGN THE WIND LOAD CHART AND INDICATE THE | | | EXTERIOR WIND PRESSURE. THEN VERIFY THE PRODUCT AND | | | GLASS TYPE SUBMITTED TO MEET THE REQUIRED EXTERIOR WIND | | | PRESSURES. FBC 107 | | | |
|