| 2019-03-11 09:31:16 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | JOSEAN A. DUPREY E.I., BN, PX |
| | BUILDING PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6716 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. THE WINDOWS PRODUCT APPROVALS SUBMITTED ARE FOR |
| | NON-IMPACT WINDOWS. THE WINDOWS INSTALLED MUST BE |
| | IMPACT OR SHUTTERS MUST BE INSTALLED. |
| | SHOW COMPLIANCE WITH FBC ? R301.2.1.2 PROTECTION OF |
| | OPENINGS. GLAZED OPENINGS IN BUILDINGS LOCATED IN |
| | WINDBORNE DEBRIS REGIONS SHALL BE PROTECTED FROM |
| | WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR |
| | WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE |
| | LARGE MISSILE TEST OF ASTM E 1996 AND ASTM E 1886 |
| | REFERENCED THEREIN, SSTD 12, TAS 201, 202 AND 203 OR |
| | AAMA 506, AS APPLICABLE. |
| | |
| | 2. IF SHUTTERS WERE INSTALLED PLEASE PROVIDE THE |
| | FOLLOWING: |
| | FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION OF |
| | OPENING PROTECTIVE DEVICES" OR PROVIDE ALL INFORMATION |
| | REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET): |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS?PAGE=2 |
| | |
| | 3. PROVIDE ALL PRODUCT APPROVALS FOR SHUTTERS, WINDOWS |
| | AND DOORS INSTALLED. FBC 107 |
| | |
| | 4. PROVIDE ROUGH OPENING DIMENSIONS FOR WINDOWS AND |
| | DOOR OPENINGS. FBC 107 |
| | |
| | |