| 2019-03-07 07:23:53 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | |
| | 1. PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF LIGHT |
| | POLES, LIGHT FIXTURES, AND CONTACTOR. FBC 107.2.1 NEC |
| | 90.7,110.2,110.3B |
| | |
| | 2. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL. PROVIDE |
| | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 3. CITY OF WPB WANTS AN ADDITIONAL CIRCUIT PULLED IN |
| | CONDUIT FOR UNSWITCHED RECEPTACLE LOCATED AT TOP OF |
| | EVERY NEW LIGHT POLE. |
| | |
| | 4. PROVIDE PULL BOX LOCATIONS ON PLANS. FBC 107.2.1 |
| | |
| | 5. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. LIGHTING AND RECEPTACLES. NEC 220. |
| | |
| | INFORMATIONAL NOTE: |
| | |
| | 1. L.E.D. LIGHING LOADS ARE TO BE CALCULATED BY AMPS |
| | NOT WATTS NEC 220.18 |
| | |
| | 2. CONTINUOUS LOADS WILL BE CALCULATED AT 125% NEC |
| | 210.19A1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |