| 2019-03-13 17:21:56 | ELECTRICAL PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. NEC 250.64 / E3607.3.1 EQUIPMENT GROUNDING CONDUCTOR |
| | REQUIRED. |
| | FBC R E3607.3 |
| | BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH |
| | CIRCUIT(S). |
| | BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) OR BRANCH |
| | CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR |
| | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH |
| | SECTION E3608. THE GROUNDING ELECTRODE CONDUCTOR(S) |
| | SHALL BE CONNECTED IN A MANNER SPECIFIED IN SECTION |
| | E3607.3.1 OR, FOR EXISTING PREMISES WIRING SYSTEMS |
| | ONLY, SECTION E3607.3.2. WHERE THERE IS NO EXISTING |
| | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) |
| | REQUIRED IN SECTION E3608 SHALL BE INSTALLED. |
| | [250.32(A)] |
| | |
| | 2. NEC 225.31 & 240.21 (B) (2) / E3706.3 DISCONNECTING |
| | MEANS. |
| | . FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR THE SUB-PANELS IN THE |
| | GUEST HOUSE. NEC 225.31, 225.32. |
| | NOTE: SHOW DISCONNECTING DEVICE ON RISER DIAGRAHM. |
| | |
| | 3. NEC TABLE 310.15 (B) (16) / TABLE E3705.1 - |
| | ALLOWABLE AMPACITY OF INSULATED CONDUCTORS. |
| | CONDUCTOR SIZE TO SUB PANEL NOT OF SUFFICIENT SIZE |
| | BASED ON THE AMPACITY OF THE MAIN DISCONNECT. |
| | NOTE: YOU MAY EITHER RE-SIZE THE CONDUCTORS BASED ON |
| | THE REFERENCED TABLES OF INSTALL A DISCONNECT AT MAIN |
| | DISCONNECT UPSTREAM OF CONDUCTORS. |
| | |
| | 4. INCLUDE VP NEXT TO THE SYMBOL AT THE VAPOR PROOF |
| | FIXTURE IN THE SHOWER AREA. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |