| Plan Review Notes For Permit 19020810 |
| Permit Number |
19020810 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-02-24 15:32:18 | 1) KITCHEN SINK CANNOT DISCHARGE INTOHORIZONTAL WET | | | VENT PERMITED 2017 FBC SEC. 912.1 | | | | | | 2) PLAN STATES CAST IRON WATER LINE. PLEASE CLARINFY | | | | | | 3) TUB NOT VENTED PROPERLY 2017 FBC SEC 910.1 FBC SEC | | | 901.2.1 | | | | | | 4) 3" CLEAN OUT IS REQUIRED IN VERTICAL WASHING MACHINE | | | STACK PER 2017 FBC SEC.708.1.5 |
|