| 2019-02-21 16:39:00 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) SHEET A 1.1 - THERE ARE NO INDICATIONS REAGARDING | | | THE MAINTENANCE OF THE LIFE SAFETY SYSTEMS DURING THE | | | SCOPE OF THE PROJECT, INCLUDING A DEMO. | | | | | | THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT CONSTRUCTION AT ALL TIMES. | | | | | | PLEASE ENSURE SYSTEMS ARE PROPERLY WORKING AND | | | MAINTAINED. | | | | | | | | | | | | 2) SHEETS A 1.1 & E 0.1 - THERE ARE NO INDICATIONS OF | | | FIRE ALARM DEVICES/EQUIPMENT AND/OR WORK ON THE FIRE | | | ALARM SYSTEM. | | | | | | ANY WORK ON THE FIRE ALARM SYSTEM DURING DEMO AND/OR | | | NEW INSTALLATION SHALL BE DONE UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS. | | | | | | ANY WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE BY A | | | CERTIFIED FIRE ALARM CONTRACTOR. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|