| 2019-03-28 13:18:12 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| | (SFHA) WITH A BASE FLOOD ELEVATION (BFE) OF 12.1 FEET |
| | NAVD88. |
| | |
| | 1. R322.2.5.1 POOLS LOCATED IN DESIGNATED FLOODWAYS. |
| | WHERE POOLS ARE LOCATED IN DESIGNATED FLOODWAYS, |
| | DOCUMENTATION SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL, WHICH DEMONSTRATES THAT THE CONSTRUCTION OF |
| | THE POOL WILL NOT INCREASE THE DESIGN FLOOD ELEVATION |
| | AT ANY POINT WITHIN THE JURISDICTION. |
| | |
| | 2. EQUIPMENT TO BE INSTALLED PER FBC R322.1.6. NOTE: |
| | APPLICANT MAY PETITION THE BUILDING OFFICIAL TO INSTALL |
| | EQUIPMENT AT FINISHED FLOOR ELEVATION. |
| | |
| | 3. DIGITAL SIGNATURES AND SEALS CANNOT BE VERIFIED. |
| | |
| | 4. POOL BARRIER SHALL COMPLY WITH FBC R4502.17.1. DOOR |
| | AND WINDOW ALARMS REQUIRED. |
| | |
| | 5. STAIR RISERS SHALL BE A MINUMUM OF 12 INCHES PER |
| | ANSI/APSP/ICC-5 2011. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |