| Plan Review Notes For Permit 19020770 |
| Permit Number |
19020770 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-04-03 15:15:56 | PLUMBING 2ND REVIEW**DENIED** | | | | | | EXISTING COMMECTS | | | | | | 1) NOT ADDRESSED. PROVIDE FLOOR PLAN DETIAL OF | | | BATHROOMS SHOW REAR GRAB BAR 12" FROM THE CENTERLINE OF | | | TOILET 36" IN OVERALL LENGHT. FBC-A 604.5.2 | | | | | | 2) ADDRESSED | | | | | | 3) ADDRESS | | | | | | 4) NOT ADDRESSED. TANKLESS WATER HEATERS WITH FACTORY | | | PRE SET TEMP ARE NOT PREMITTED. FBC-P 607.1.1. UNIT | | | EITHER SHALL HAVE A ASSE 1070 VALVE BUILT IN OR A 1070 | | | DEVICE ADDED TO COMPLY WITH FBC-P 607.1.2. THE MODEL | | | SPEC ON PLANS DOES NOT MEET THE INTENT OF THE PLUMBING | | | CODE. | | | | | | NEW COMMENT | | | | | | 5) SIDE GRAB BAR IS SHOWING 11" OFF REAR WALL 42" IN | | | LENGTH GIVING AN OVERALL OF 53". THE MIN DISTANCE FROM | | | THE BACKWALL ALLOWED IS 54". SEE FBC-A 604.5.1 FOR | | | DETAIL. YOUR BAR MUST BE MOUNTED @ 12" OFF BACKWALL TO | | | COMPLY. SEE PLAN DETAIL SHT. A2.0 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | |
|