| Plan Review Notes For Permit 19020770 |
| Permit Number |
19020770 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-04-01 10:26:24 | 4/1/19 | | | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | | | | 1) SHEET E 1 0 - THERE ARE NO INDICATIONS OF FIRE ALARM | | | DEVICES/EQUIPMENT WITHIN THE PAVILION. | | | | | | IF THERE IS AN EXITING FIRE SYSTEM WITHIN THE PAVILION, | | | THE NEW RESTROOMS SHALL HAVE SYSTEM DEVICES EXTENDED | | | INTO THEM. | | | | | | ANY WORK ON A FIRE ALARM SYSTEM SHALL BE DONE UNDER | | | SEPARATE PERMITTED SHOP DRAWINGS BY CERTIFIED FIRE | | | ALARM CONSTRACTORS. | | | | | | IF THERE IS NO FIRE ALARM SYSTEM IN THE PALVILION, | | | PLEASE DISREGARD. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|