| 2019-03-09 07:35:50 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE. THE BAR SHOWN ON THE PLAN |
| | DOES NOT GIVE YOU THE 24" OFF CENTERLINE OF TOILET. PER |
| | FBC ACC 604.5.2 |
| | |
| | 2. THE OUTLET OF THE TOILET PAPER DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR. THE DETAIL ON THE PLAN DOES NOT SHOW THE OUTLET |
| | DIMENSION. PER FBC ACC 604.7 |
| | |
| | 3. A WATER FOUNTAIN IS REQUIRED WITHIN 500' OF LOCATION |
| | SHOW ON THE PLAN OR PROVIDE ONE. PER FBC PL 403.5 |
| | |
| | 4.TEMPERED WATER SHALL BE DELIVERED BY A TEMPERATURE |
| | LIMITING DEVISE COMPILING WITH ASSE 1070. PER FBC ACC |
| | 416.5 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |