| 2019-02-26 07:37:50 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19020770 |
| | ADD: 1301 SUMMIT BLVD. |
| | CONT: GAST |
| | TEL: 561-281-1001 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. FEB. 26/ 2019 |
| | ACTION: DENIED |
| | 1) PLEASE BE AWARE THAT THE PAVILION/ ENCLOSURE THAT |
| | THIS PERMIT IS FOR IS LOCATED IN A AE FLOOD ZONE. THE |
| | BFE (BASE FLOOD ELEVATION IS 12.2 NAV88). SINCE ALL |
| | PERMITS PULLED FOR ALL BUILDINGS ARE UNDER THIS ONE |
| | ADDRESS (1301 SUMMIT) PLEASE PROVIDE DOCUMENTATION THAT |
| | IS AND ALL OTHERS BEFORE FOR THIS STRUCTURE ARE NOT A |
| | SUBSTANTIAL IMPROVEMENT. |
| | SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR |
| | FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR, |
| | RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE |
| | CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR |
| | EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT |
| | OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF |
| | NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE. THE |
| | ORIGINAL PERMIT FOR THIS STRUCTURE IS 99100341 AND THE |
| | VALUE OF $100,000.00 DOLLARS IN VALUE. |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 |
| | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. (8) FLOOD REQUIREMENTS ELEVATIONS, |
| | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. |
| | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 |
| | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON |
| | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND |
| | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION |
| | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL. |
| | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & |
| | CONTROL. FBC BUILDING 1612 AND CITY OF WPB CODE OF |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | REQUIRE AN ADDITIONAL 6 INCHES/ (12 INCHES OF ELEVATION |
| | IF PERMIT APPLICATION AFTER SEPT. 12/2016, AFTER OCT. |
| | 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE BOARD WILL BE |
| | REQUIRED OR (2) FEET ABOVE BASE FLOOD. |
| | |
| | 2) SHEET A-2.0: |
| | |
| | 2A) SECTION 1 INDICATES A 2X6 LEDGER BUT THE PLAN DOES |
| | NOT INDICATE THE SIZE OF THE FRAMING MEMBERS. SHEET |
| | A-1-0 DOES PROVIDE THE SPACING OF THE FRAMING MEMBERS |
| | BUT NOT THE SIZE. SEE 2017 FBC-B TABLE 2308.7. |
| | |
| | 2B)(1) PLEASE NOTE IN SECTION 1 OF THIS PLAN A LOUVER |
| | TO THE EXTERIOR IS SHOWN, PLEASE PROVIDE A PRODUCT |
| | APPROVAL FOR THIS LOUVER IN COMPLIANCE WITH: 2017 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: (31(C) WALL LOUVERS, |
| | |
| | 2B)(2) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE |
| | CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3)SHEET A-2-0, THE DETAILS 1, 3, 4 & 8 ALL SHOW WALL |
| | ELEVATIONS OF THE RESTROOMS WITH THE WATER CLOSET BUT |
| | THEY DO NOT PROVIDE THE DISTANCE FROM THE CORNER NOR |
| | THE LENGTH OF THE GRAB BARS OR COMPLIANCE WITH THE 2017 |
| | FBC-ACCESSIBILITY CODE SECTIONS: |
| | 604.5 GRAB BARS. |
| | 605.1 SIDE WALLS. |
| | 605.2 REAR WALLS. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |