| 2020-08-19 11:32:13 | FAILED |
| | |
| | PERMIT 19020748 - UNDERGROUND FIBER MCIMETRO PROJECT |
| | #1806CQCB.6 800 BLOCK OF CHASE - 3RD RESUBMITTAL |
| | |
| | PROVIDE WRITTEN RESPONSE TO COMMENTS. |
| | |
| | THE FOLLOWING ITEMS NEED TO BE ADDRESSED OR THE PERMIT |
| | WILL NOT BE APPROVED. |
| | |
| | 1) ENGINEERING PLAN - |
| | |
| | A. STAFF HAS REVIEWED AN ELECTRICAL PERMIT FOR A |
| | PROPOSED VERIZON WIRELESS FACILITY; HOWEVER, IT WAS ON |
| | THE NORTHEAST CORNER OF THIS INTERSECTION, NOT THE |
| | NORTHWEST CORNER AS INDICATED ON THESE PLANS. PLEASE |
| | VERIFY THE POLE LOCATION IN CASE IT AFFECTS YOUR PLANS. |
| | |
| | B. OTHER FIBER PLANS THAT YOU HAVE SUBMITTED INCLUDE |
| | THE NOTE THAT THE TREE GRATE/PLANTING AREA MAY NOT BE |
| | USED TO ASSIST IN THE BORE. PLEASE INCLUDE THIS NOTE ON |
| | THE PLANS WITH THIS PERMIT. |
| | |
| | C. THE BORE SHOWN AT THREE (3) FEET BELOW GRADE IS AT A |
| | SUFFICIENT DEPTH SINCE THERE ARE NO TREES BETWEEN THE |
| | HANDHOLES. |
| | |
| | PLEASE NOTE: |
| | |
| | THE INSTALLATION CONTRACTOR MUST CONTACT SUNSHINE 811 |
| | TO VERIFY THE LOCATION OF ALL UTILITIES AND VERIFY ALL |
| | DEPTHS PRIOR TO CONSTRUCTION. ALL CITY UTILITIES MUST |
| | BE LOCATED BY SOFT DIG METHODS BEFORE STARTING THE |
| | WORK. |
| | |
| | THE RIGHT-OF-WAY USE PERMIT REQUIRES YOU TO PROVIDE A |
| | CERTIFICATE OF LIABILITY INSURANCE, WHICH IN ACCORDANCE |
| | WITH SECTION 78-406 OF THE CITY CODE SPECIFICALLY NAMES |
| | THE CITY OF WEST PALM BEACH, ITS COMMISSIONERS, |
| | OFFICERS, EMPLOYEES AND AGENTS AS ADDITIONAL INSURED. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |