| 2019-03-13 14:55:06 | PLUMBING 1ST REVIEW**DENIED**03/13/2019 |
| | |
| | 1) SEE BUILDING PLAN REVIEWERS COMMENTS 1A, 1B, 1C. IF |
| | THE OCCUPANT LOAD IS 16 THEN 2 RESTROOMS WILL BE |
| | REQUIRED TO COMPLY WITH FBC-P403. A MOP SINK AND HI-LOW |
| | DRINKING FOUNTAIN WOULD ALSO BE REQUIRED UNDER FBC-P |
| | 410.3 AND FBC-A 211.2 |
| | |
| | 2) BREAK ROOM SINK MUST BE ACCESSIBLE. SHOW CLEAR FLOOR |
| | SPACE 30" BY 48" FOR FRONT APPROACH AND COUNTER TOP MAX |
| | HEIGHT WOULD BE 34". FBC-A 305, 306. SHT. A-4.0 CALLS |
| | OUT 36" MIN. |
| | |
| | 3) PROVIDE CLEAR FLOOR SPACE FOR THE TOILET AND |
| | LAVATORY ON THE PLAN. FBC-A 305, 306. FBC 107.3.5 |
| | |
| | 4) SHT A-4.0 #1 TOP LEFT CALLS OUT TOILET 1" 1 1/2" (13 |
| | 1/2") FROM SIDE WALL. THE TOILET SHALL BE 16" TO 18" |
| | FBC-A 604.2 |
| | |
| | 5) LAVATORY CALLED OUT ON SHT.P-1 IS 21 1/4" BY 22" AND |
| | MAY ENCROACH INTO THE TOILETS CLEAR FLOOR SPACE AND NOT |
| | ALLOW THE MIN 15" FROM THE SIDE WALL WITH THE ROOM |
| | OVERALL ROUGH @ 7' 2". MIN SINK SIZE ALLOWED IS 19" BY |
| | 21. FBC-A604.8.1.6 AND FBC-P 405.3.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |
| | |