| Plan Review Notes For Permit 19020741 |
| Permit Number |
19020741 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-03-19 10:34:37 | PLAN DENIED | | | 1) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S | | | 2017 FBC (M) PAGE A-5.0 SHAW'S WOOD DOOR ON | | | AIR HANDLER CLOSET. | | | 2) REFER TO SECTION 601.6 BALANCED RETURN AIR | | | 2017 FBC (M) | | | 3) PROVIDE OUTDOOR AIR TO MEET TABLE 403.3.1.1 | | | MINIMUM VENTILATION RATES 2017 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|