| 2019-03-08 18:57:26 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- EXISTING PARTIAL FLOOR PLAN SHOWS EXISTING "GUEST |
| | ROOM". THERE ARE NO PERMITS FOR THE CONVERSION OF THIS |
| | SPACE TO A GUEST ROOM. THERE IS AN EXPIRED PERMIT |
| | (#04070675) FOR THE CONVERSION OF THE EXISTING CARPORT |
| | TO GARAGE. THE PERMIT IS EXPIRED. THE EXPIRED PERMIT |
| | NEEDS TO BE TAKEN CARE OF SINCE IT LOOKS LIKE SOME WORK |
| | WAS DONE, BUT THERE WERE NO INSPECTIONS. AND, NOW PLANS |
| | SUBMITTED SHOW THAT IT LOOKS LIKE THERE WAS ADDITIONAL |
| | WORK DONE WITHOUT PERMITS. ACCORDING TO PLANS |
| | SUBMITTED, THE PROPOSED GARAGE WAS CONVERTED TO A |
| | BEDROOM. THE EXPIRED PERMIT CAN BE INCORPORATED INTO |
| | THIS PERMIT APPLICATION IF ALL WORK THAT WAS DONE |
| | WITHOUT PERMIT IS REFLECTED ON THE PLANS SUBMITTED NOW |
| | AND SHOW EVERYTHING AS NEW INSTEAD OF EXITING. THIS WAY |
| | THE EXPIRED PERMIT MAY BE REVOKED AND THE PROPER |
| | INSPECTIONS CAN BE PERFORMED. SEC. 105.1 CITY |
| | AMENDMENTS. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 1106 FBC-EXISTING BUILDING. AND SEC. R101.4.2 |
| | AND R101.5 FBC-ENERGY CONSERVATION. |
| | |
| | 3- BEDROOM EGRESS WINDOWS DON'T COMPLY WITH THE CLEAR |
| | OPENING REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. |
| | SINGLE HUNG WINDOW #1 SHOWN ON THE WINDOW SCHEDULE (37 |
| | X 52.5) DOESN'T PROVIDE THE MIN. CLEAR HEIGHT OPENING |
| | OF 24". ALSO, OPENING DIMENSIONS SHOWN ON THE "INFILLED |
| | GARAGE DOOR OPENING ELEVATION" ON SHEET S2 DON'T SEEM |
| | TO WORK WITH PROPOSED WINDOW SIZE. COORDINATE |
| | DIMENSIONS WITH REQUIRED EGRESS WINDOW SIZE. |
| | |
| | 4- STRUCTURAL WALL SECTIONS PROVIDED ARE MISSING SOME |
| | INFORMATION. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS ON ALL WALL SECTIONS PROVIDED. CLEARLY |
| | SPECIFY TOP AND BOTTOM CONNECTIONS FOR ALL FRAMING |
| | MEMBERS. CLEARLY SPECIFY ALL CONNECTORS SHOWN ON THE |
| | "INFILLED GARAGE DOOR OPENING ELEVATION" ON SHEET S2. |
| | SEC. R601.2 FBC-RESIDENTIAL. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL) |
| | |
| | A)SINGLE HUNG WINDOWS. INFORMATION SUBMITTED IS |
| | INCOMPLETE. NEED TO PROVIDE COMPLETE FLORIDA PRODUCT |
| | APPROVAL (2 COPIES), INCLUDING THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE THAT CORRESPONDS TO THE DRAWINGS |
| | SUBMITTED. THE FLORIDA PRODUCT APPROVAL IS REQUIRED |
| | BECAUSE IT SHOWS IF PRODUCT IS APPROVED AND CURRENT |
| | CODE IN EFFECT. |
| | |
| | 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. REVISE AS REQUIRED OR PROVIDE COPY OF |
| | SIGNED CONTRACTS INCLUDING THE DESIGN PROFESSIONAL |
| | FEES. |
| | |
| | 7- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR |
| | REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW |
| | COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| | REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |