Plan Review Notes
Plan Review Notes For Permit 19020686
Permit Number 19020686
Review Stop P
Sequence Number 2
Notes
Date Text
2019-07-30 16:27:27PLUMBING COMMENTS: APPROVED WITH PROVISO
 1.NEW GARAGE PLAN SHEET GS-1: PLUMBING RISER DIAGRAM IS
 CODE COMPLIANT.
 2. NEW HOUSE PLAN SHEET P-1 COMMENTS NOTED ARE REDLINED
 ON THE PLAN AND NO ACTION IS EREQUIRED.
 A.SANITARY RISER DIAGRAM
 B.CLOTHES WASHER AND SINK SHALL CONNECT TO BUILDING
 DRAIN DOWNSTREAM OF THE BATHROOM FIXTURES TO COMPLY
 WITH FBC RES P3108.1
 C.CONNECT FIXTURE DRAIN OF SINK TO VERTICAL WASTE PIPE
 AT A POINT ABOVE THAT OF THE CLOTHES WASHER AND COMPLY
 WITH FBC RES 3107.3.
 E.ELIMINATE LOOP VENT AT HIS BATH AND COMPLY W/ FBC RES
 P3108.1.
 F.IN HER BATH, CONNECT TUB WASTE AND SHOWER WASTE
 INDEPENDENTLY TO WET VENT AND SIZE WET VENT BETWEEN
 SHOWER AND WATER CLOSET DRAIN 3? TO COMPLY WITH FBC RES
 P3108.1.
 G.RECONCILE FLOOR PLAN PIPING LAYOUT WITH SANITARY
 RISER.
  
 A SEPARATE GAS PERMIT AND PLANS ARE REQUIRED
  