| 2019-07-30 13:28:16 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS PER THE FORMAT IN FBC RES. THIS SHOULD INCLUDE |
| | THE AMOUNT DETERMINED FOR GARAGE UNDER SEPARATE PERMIT. |
| | ALSO, IT APPEARS THE AC LOAD WAS NOT INCLUDED IN TOTAL. |
| | NEC 220; FBC RE E3602.2 (NOT CORRECTED. LOOK AT THE |
| | MATH OF THE CALCULATION. A TOTAL OF 20432 WATTS IS |
| | SHOWN. HOWEVER, WHEN YOU ADD THE TOTAL OF 16,500 FOR |
| | AC/AHU, 10,000 FOR THE FIRST 10K, AND 10432 FOR THE |
| | REMAINDER AT 40%, THIS EQUALS MORE THAN 20,432. PROVIDE |
| | CORRECTION AS REQUESTED.) |
| | 2. PLAN SHOWS THE GARAGE FEED COMING DIRECTLY FROM |
| | METER CAN AS UNFUSED CONDUCTORS. THIS INSTALLATION |
| | WOULD MEAN THE MAINS FOR THIS ADDRESS ARE IN 2 |
| | DIFFERENT LOCATIONS, WHICH IS A CODE VIOLATION. MAINS |
| | MUST BE GROUPED. PROVIDE CORRECTION. NEC 230.72: FBC RE |
| | E3601.7 (MAINS ARE STILL SHOWN IN TWO DIFFERENT |
| | LOCATIONS. THE RISER DIAGRAM DOES NOT MATCH WHAT IS |
| | SHOWN ON PLAN. PROVIDE CORRECTIONS.) |
| | 3. RISER DIAGRAM SHOWS A FEED FROM THE METER TO THE |
| | INTERIOR PANEL WHICH IS LOCATED IN THE GARAGE. |
| | CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR |
| | DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE |
| | IN THIS FASHION. PROVIDE EITHER A MAIN ON THE OUTSIDE |
| | OF THE HOME, OR INSTALL THE CONDUCTORS UNDER THE SLAB. |
| | PROVIDE CORRECTIONS. NEC 230.70, 250.6; FBC RE E3601.6 |
| | (NOT CORRECTED. SEE COMMENT 2.) |
| | 4. WIRE SIZE SHOWN FROM METER CAN TO PANELS IS NOT |
| | SIZED PROPERLY. WIRE SIZES FROM NEC 310.15(B)(7), OR |
| | FBC RE E3603.1, CAN ONLY BE USED WHEN THE SERVICE |
| | CONDUCTOR SUPPLIES 100% OF THE LOAD. SINCE THIS IS NOT |
| | THE CASE, PROVIDE CORRECTED WIRE SIZE FROM METER CAN TO |
| | PANELS. NEC 310.15(B)(7) AND (B)(16); FBC RE E3603.1, |
| | E3705.1 (WIRE TO MAIN PANEL SHOWS THREE 3/0 AND ONE 1/0 |
| | CONDUCTOR, BUT THIS IS NOT A THREE PHASE SYSTEM. THERE |
| | SHOULD NOT BE A EQUIPMENT GROUND FROM THE METER TO THE |
| | FIRST MEANS OF DISCONNECT.) |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |