| 2019-03-12 12:39:50 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1-PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | FBC R 401.3 (DRAINAGE) |
| | FBC 107.2.5 (SITE PLAN) |
| | FBC 110.9 (IMPACT OF CONSTRUCTION) |
| | |
| | 2- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY |
| | SEC. R401.4 FBC-RESIDENTIAL. |
| | |
| | 3- SHEET A-2: |
| | A) REVISE WIND DESIGN BASIS INFORMATION. ACCORDING TO |
| | SEC. R301.2.1.4 FBC-RESIDENTIAL, THIS BUILDINGS ARE |
| | LOCATED IN EXPOSURE "D" NO EXPOSURE "B". REVISE AS |
| | REQUIRED AND REVISE THE WALL PRESSURES SHOWN ON SHEETS |
| | A-2 AND A-3 ALSO. |
| | NOTE: THIS APPLIES TO DRAWINGS FOR THE DETACHED GARAGE |
| | ALSO. |
| | |
| | B) REVISE THE WALL ELEVATION DIMENSION "A" SHOWN ON THE |
| | WIND DESIGN BASIS. ACCORDING TO FIGURE R301.2(7) |
| | FBC-RESIDENTIAL THE END ZONE "A" IS 4 FEET NO 3 FEET. |
| | REVISE AS REQUIRED. |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | "SPECIAL FRAMING" AT THE COVERED PATIO SLIDING GLASS |
| | DOORS . SPECIFY ALL FRAMING MEMBERS AND ALL CONNECTORS. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 5- REVISE ATTIC ACCESS SECTION #2 ON SHEET A-1. NEED |
| | 22" MIN. FOR FRAMED OPENING NOT 21". SEE SEC. R807.1 |
| | FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| | |
| | 6- REAR PATIO SECTION #4 ON SHEET A-4: |
| | A) PROVIDE SPECIFICATIONS FOR CONCRETE DECK FINISH |
| | (SEC. R903.1 FBC-RESIDENTIAL. |
| | |
| | B) PROVIDE DETAILS AND SPECIFICATION FOR CEILING |
| | CONSTRUCTION. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 7-SPECIFY PITCH OF CONCRETE DECK ABOVE COVERED PATIO. |
| | TYPICALLY, LOW SLOPE ROOF REQUIRE AT LEAST 1/4" PER |
| | FOOT SLOPE. SEC. R905.11 FBC-RESIDENTIAL. NOTE: |
| | COORDINATE WITH ROOF COVERING SPECIFIED ON PLANS. NOTE: |
| | BUILDING SECTION A ON SHEET A-4 SPECIFIES 1" SLOPE |
| | MINIMUM. THIS SLOPE DOESN'T COMPLY. REVISE AS REQUIRED. |
| | |
| | 8- WALL SECTIONS ON SHEET A-4: SPECIFY THE MINIMUM 12" |
| | FOOTING DEPTH AS REQUIRED BY SEC. R403.1.4 |
| | FBC-RESIDENTIAL. |
| | |
| | 9- PROVIDE SPECIFICATIONS FOR INSULATION BETWEEN GARAGE |
| | AND THE A/C AREA. SEC. R103.2 FBC-ENERGY CONSERVATION. |
| | NOTE: THIS APPLIES TO DETACHED GARAGE ALSO. |
| | |
| | 10- DETACHED GARAGE: PROVIDE SPECIFICATIONS FOR FIRE |
| | RATED DOOR BETWEEN THE GARAGE AND THE OFFICE/WORK SHOP |
| | AREA. SEC. R302.5.1 FBC-RESIDENTIAL. |
| | |
| | 11- ENERGY CALCULATIONS (MAIN HOUSE): |
| | A)THE ENERGY FORM R405-2017 IS REQUIRED TO BE CERTIFIED |
| | AT THE BOTTOM BY THE OWNER OR OWNER?S LEGALLY |
| | DESIGNATED AGENT PRIOR TO RECEIVE THE PERMIT AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | 6TH EDITION (2017). |
| | |
| | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER NAME, BUILDER NAME, PERMIT OFFICE AND |
| | JURISDICTION NUMBER (THIS JURISDICTION IS 604700) . |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | C) PROVIDE WINDOWS AND DOORS MANUFACTURER'S |
| | SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR |
| | SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7 ON PAGE |
| | 1 OF 5 AS REQUIRED BY SEC. R405.4.3 FBC-ENERGY |
| | CONSERVATION. NOTE: COORDINATE WITH PLANS AND PRODUCT |
| | APPROVALS SUBMITTED TO AVOID CONFLICTS/DELAYS. |
| | |
| | D)REVISE ITEM #9(B) AND #9(C). THE MATERIAL OF ADJACENT |
| | WALL FRAME IS NOT WOOD. SEE PLANS AND REVISE AS |
| | REQUIRED. COORDINATE R-VALUE WITH PLANS. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E)TYPICALLY THE THE ATTIC VENT RATIO IS 1/150. PAGE 2 |
| | OF 5 SPECIFIES 1/300. PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH THE EXCEPTION OF |
| | SEC. R806.2 FBC-RESIDENTIAL WHEN SPECIFYING A VENT |
| | RATIO OF 1/300 AS SHOWN ON PAGE 2 OF 5. NOTE: |
| | COORDINATE WITH PLANS TO AVOID CONFLICTS/DELAYS.F) |
| | |
| | F) REVISE THE DOORS INFORMATION SHOWN ON PAGE 3 OF 5 TO |
| | MATCH PLANS. WHY COUNTING THE GARAGE OVERHEAD DOORS?. |
| | ONLY THE DOORS SEPARATING A/C FROM THE NON-A/C AREAS |
| | ARE CONSIDERED. THE GARAGE IS NO PART OF THE A/C AREA |
| | OF THIS HOUSE. SEE A/C AREA ON FRONT PAGE. REVISE AS |
| | REQUIRED. DELETE THE GARAGE DOORS. |
| | |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | G) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5 |
| | TO MATCH PLANS. REVISE ORIENTATION, WINDOW AREA AND |
| | OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | H)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| | (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| | CONSERVATION. |
| | |
| | NOTE: |
| | LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS |
| | ARE NOT USING THE DEFAULT FACTOR. |
| | |
| | 12)ENERGY CALCULATIONS (DETACHED GARAGE): |
| | A) ITEM #4 IS INCORRECT. ACCORDING TO PLANS THERE IS |
| | NOT BEDROOM. REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | B) ITEM #6 IS INCORRECT. ACCORDING TO PLANS THE A/C |
| | AREA IS 411 S.F. NOT 561 S.F. REVISE AS REQUIRED. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | C) MISSING INFORMATION ABOUT THE ADJACENT WALL. |
| | COORDINATE WITH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | D) SPACES INFORMATION ON PAGE 2 OF 4 SPECIFIES THAT |
| | THERE IS A KITCHEN. ACCORDING TO PLANS THERE IS NOT |
| | KITCHEN. REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E) REVISE WINDOWS INFORMATION ON PAGE 3 OF 4 TO MATCH |
| | PLANS. REVISE WINDOW ORIENTATION. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | F) REVISE ALL OTHER COMMENTS LISTED FOR THE MAIN HOUSE |
| | ABOVE AND THAT APPLY TO THIS BUILDING. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | 13-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL) |
| | |
| | A)ENTRY DOORS |
| | B)EXTERIOR SWING DOORS. |
| | C)SINGLE HUNG WINDOWS. |
| | D)WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY |
| | SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE |
| | WITH THE CALCULATED DESIGN PRESSURES. |
| | E)OVERHEAD GARAGE DOORS. |
| | F)POCKET SLIDING GLASS DOORS AS SHOWN ON PLANS. |
| | G)PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | H) METAL ROOF AS SPECIFIED ON PLANS. |
| | |
| | 14-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 15- HANDRAILS AND GUARDRAILS |
| | A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | INTERIOR HANDRAILS AND GUARDRAIL AND FOR BALCONY |
| | GUARDRAIL SHOWING COMPLIANCE WITH TABLE R301.5, SEC. |
| | R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL. |
| | NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE |
| | DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC. |
| | R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS |
| | THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW |
| | PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED |
| | BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL |
| | TO THIS OFFICE. |
| | |
| | 16- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR THE |
| | CONSTRUCTION AND INSTALLATION OF THE DECORATIVE |
| | ALUMINUM SHUTTERS SHOWN ON THE FRONT ELEVATION OF THE |
| | MAIN HOUSE. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | 17- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. VALUATION WAS UPDATED TO $495,627 TOTAL FOR |
| | MAIN HOUSE AND DETACHED GARAGE. THE PERMIT FEE BALANCE |
| | IS $9,167.71. |
| | |
| | |
| | 18-PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR |
| | REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW |
| | COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| | DRAWINGS/DOCUMENTS FOR REFERENCE. |
| | |