Plan Review Notes
Plan Review Notes For Permit 19020679
Permit Number 19020679
Review Stop P
Sequence Number 2
Notes
Date Text
2019-03-05 08:52:52PLUMBING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NEW COMMENTS
  
 1. REFERENCE PLUMBING RISER SUBMITTED -
 1A. PROVIDE PIPE SIZE FOR WATER CLOSET
 1B. PROVIDE PIPE SIZE FOR TUB AND LAV
 1C. PROVIDE PIPE SIZE FOR DOUBLE LAV
 1D. PROVIDE PIPE SIZE FOR TUB, SHOWER, LAV
  
 2. VENT REQUIRED AT TUB, SHOWER, LAV COMBO.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  