Plan Review Notes
Plan Review Notes For Permit 19020679
Permit Number 19020679
Review Stop E
Sequence Number 2
Notes
Date Text
2019-03-05 09:58:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. VALUE NEEDS TO REFLECT WHAT A CONTRACTOR WOULD
 CHARGE FOR THIS INSTALLATION, TO INCLUDE LABOR AND
 MATERIALS. PROVIDE CORRECTED VALUE. WPB FBC 109.3
 (BUILDING REVIEWER WILL DISCUSS THIS WITH OWNER.)
 2. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2 (ANY SHEETS THAT ARE
 SUBMITTED AS PART OF THE DESIGN, INCLUDING THE "KITCHEN
 REMODEL DETAILS", MUST BE SIGNED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION.)
  
 NEW COMMENTS:
  
 3. NEW PLAN PROVIDED SHOWS TWO GFCI RECEPTACLES ON THE
 ISLAND HAVE BEEN REMOVED. THE REMAINING TWO RECEPTACLES
 ARE ON THE SIDE OF THE ISLAND WHERE THE COUNTER TOP
 EXTENDS OVER ITS SUPPORT BASE, IF THE COUNTER TOP
 EXTENDS MORE THAN 6 INCHES OVER THE SUPPORT BASE THESE
 RECEPTACLES WILL NOT COUNT FOR THE REQUIRED RECEPTACLES
 IN THAT LOCATION. PROVIDE CLARIFICATION THAT THE
 COUNTER TOP EXTENDS LESS THAN 6 INCHES, OR SHOW THE
 RECEPTACLES IN A LOCATION WHERE THE COUNTER TOP DOES
 NOT EXTEND 6 INCHES OR MORE. NEC 210.52(C)(5); FBC RE
 E3901.4.5
 4. NEW SHEET PROVIDED STATES THERE WILL BE NEW CIRCUITS
 RUN FROM PANEL. PROVIDE PANEL SCHEDULE INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 210.20, 215.5, 408.4; WPB FBC 107.3.5; FBC RE
 E3706.2, E3902
 5. PICTURE SHOWS A HOOD ABOVE THE RANGE, BUT I SEE NO
 ELECTRICAL FOR THE HOOD LISTED ON PLAN. WILL THIS BE A
 DEDICATED CIRCUIT? PROVIDE CLARIFICATION. WPB FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER