| 2019-03-05 09:58:25 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. VALUE NEEDS TO REFLECT WHAT A CONTRACTOR WOULD |
| | CHARGE FOR THIS INSTALLATION, TO INCLUDE LABOR AND |
| | MATERIALS. PROVIDE CORRECTED VALUE. WPB FBC 109.3 |
| | (BUILDING REVIEWER WILL DISCUSS THIS WITH OWNER.) |
| | 2. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF |
| | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR |
| | THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC |
| | 107.1, 107.2.1, 107.3.5.1.2 (ANY SHEETS THAT ARE |
| | SUBMITTED AS PART OF THE DESIGN, INCLUDING THE "KITCHEN |
| | REMODEL DETAILS", MUST BE SIGNED BY THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION.) |
| | |
| | NEW COMMENTS: |
| | |
| | 3. NEW PLAN PROVIDED SHOWS TWO GFCI RECEPTACLES ON THE |
| | ISLAND HAVE BEEN REMOVED. THE REMAINING TWO RECEPTACLES |
| | ARE ON THE SIDE OF THE ISLAND WHERE THE COUNTER TOP |
| | EXTENDS OVER ITS SUPPORT BASE, IF THE COUNTER TOP |
| | EXTENDS MORE THAN 6 INCHES OVER THE SUPPORT BASE THESE |
| | RECEPTACLES WILL NOT COUNT FOR THE REQUIRED RECEPTACLES |
| | IN THAT LOCATION. PROVIDE CLARIFICATION THAT THE |
| | COUNTER TOP EXTENDS LESS THAN 6 INCHES, OR SHOW THE |
| | RECEPTACLES IN A LOCATION WHERE THE COUNTER TOP DOES |
| | NOT EXTEND 6 INCHES OR MORE. NEC 210.52(C)(5); FBC RE |
| | E3901.4.5 |
| | 4. NEW SHEET PROVIDED STATES THERE WILL BE NEW CIRCUITS |
| | RUN FROM PANEL. PROVIDE PANEL SCHEDULE INDICATING ANY |
| | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 210.19, 210.20, 215.5, 408.4; WPB FBC 107.3.5; FBC RE |
| | E3706.2, E3902 |
| | 5. PICTURE SHOWS A HOOD ABOVE THE RANGE, BUT I SEE NO |
| | ELECTRICAL FOR THE HOOD LISTED ON PLAN. WILL THIS BE A |
| | DEDICATED CIRCUIT? PROVIDE CLARIFICATION. WPB FBC |
| | 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |