| Date |
Text |
| 2019-04-09 11:52:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19020678 |
| | 4/9/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW HEAT PUMP IN ACCORDANCE WITH SECTION C403.2.1 FBC |
| | EC. |
| | |
| | 2) SHEET M201: PROVIDE EXHAUST VENTILATION CALCULATIONS |
| | FOR THE LOCKER AND TOILET ROOMS- TABLE 403.3.1.1 FBC M. |
| | |
| | 3) M101: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY |
| | SYSTEM OF THE NEW AHU-1- SECTION 606.2.1 FBC M. |
| | |
| | 4) M101: SHOW THE WATER SERVICE POINTS OF CONNECTIONS |
| | TO AHU-1 |
| | |
| | 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR AHU-1- |
| | SECTION 307.2.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |